INSTALLATION GUIDE

Product code

I

n Al

I

n Cu

U

n

I

max Al

I

max Cu

U

max

VG03-0006

160 A

200 A

1000 V

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

Screw size

Screw 

1

M10

Tightening torque 

M

50-70 mm²

10 Nm

20 mm

 SW

1

5

(M

/ M

H1 

/ M

H2

)

25-35 mm²

6 Nm

 

(output) 

L

2

12 mm

Screw 

2

M6

2,5-16 mm²

3 Nm

 SW

2

3

-

-

Screw 

3

-

Max. Input cable

70 mm²

 SW

3

-

Max, Output cable

16 mm²

1,5 mm2

2,5 mm2

6 mm2

10 mm2

16 mm2

25 mm2

35 mm2

50 mm2

0

0 / 3 / 3

0 / 2 / 2

3 / 1 / 1

3 / 1 / 1

2 / 0 / 0

2 / 0 / 0

1 / 0 / 0

70 mm2

95 mm2

120 mm2

150 mm2

185 mm2

240 mm2

300 mm2

400 mm2

1 / 0 / 0

0

0

0

0

0

0

0

Product data

Product name

OJL-connector 200

Installation

 
 
 
 

DIN-rail and screw mounting

Cross-section of conductors and number of conductors/ space. ( S / H1 / H2 ) 

Connection

Stripping lenght (input) 

L

1

The conductors number on table 
refer only to industrially installed 
terminals.

L

1,2

DIN-rail mounting

Set the connector to DIN-rail. 
See picture.
Push until ”click”

Mounting with screw. 

Max. Ø 5

Removing from DIN-rail

Release the slider part with 
screwdriver.  Lift the 
connector.

Input

S

Output

H

1

Output

H

2

M

S

M

H2

M

H1

Screw

1

SW

1

Screw

2

SW

2

SW

1,2

Sc

re

w

1

,2

Connect  the 

input

conductor when  cover is open. Can be used for both copper- or aluminium 

conductors. Note! The Aluminium conductor is allowed only one conductor/one space. 
With the Al-conductors, it's recommended to use anti-corrosion paste. (i.e. Penetrox)
We recommend a ferrule when using a fine-stranded conductor.

The branching conductors 

H1

and 

H2

can be connected also when 

the cover is closed. Note! It's allowed use only Cu-conductors for 
branching.