SERVICE MENU: “FLOW DIRECTION”
Make settings if the supply air and extract air are connected on the right or left hand.
Press again and then in order to choose
Left
or
Right
.
SERVICE MENU: “FREEZE PROTECTION”
(NOT USED)
Setting of limit value when freeze protection sensor is installed. The sensor (GT5) is installed at the return pipe
on the heating coil. When 3°C higher than set point the valve opens completely. If the temperature continues
to fall to set point the unit will stop, but the valve remains open and the pump output remains active.
Press again and then in order to choose
Limit
: (5°C-10°C).
Press again and then in order to choose ’InOutDiff’
:
(1°C-10°C),
Extract HI:
(19°C-26°C)
and
Extract LO:
(18°C-24°C).
SERVICE MENU: “SUMMER COOLING”
If
”Summer Cooling” ”On”
is chosen, the Summer cooling is activated when the extract air temperature is
higher than ”Extract HI” (19°C-26°C) and outside air is colder than ”Extract - ‘In OutDiff’ (1°C-10°C
difference between the temperature outside and extract air)”.
Summer cooling is deactivated when exhaust air temperature is lower than ”Extract LO” (18°C-24°C)
or when the outside temperature is warmer than ”Extract air - ’InO 1,0ºC’ ”.
If Summer Cooling is activated, water cooling is disabled.
Press again and then in order to choose
On
or
Off
. In order to go forward in “Summer Cooling” press .
Cont.
Cont. next line.
5
5
5
5
Regulation mode
Modbus
Extract
Extract
Extract
Extract
Extract
Extract
Extract
Extract
Modbus
Summer cooling
Sensor calibration
1270421_utg2_HERU_K_SV_EN.pdf 63
2018-03-12 10:00:26
Содержание HERU 70 K EC
Страница 1: ...SVENSK ENGLISH VERSION Montage installationsanvisning Assembly Installation instructions HERU K...
Страница 11: ...11 UPPSTART H GERUTF RANDE V NSTERUTF RANDE Avluft Tilluft Tilluft Avluft Fr nluft Uteluft Uteluft Fr nluft...
Страница 12: ...12 REGLERSCHEMA HERU K SOM VISAR SAMTLIGA GIVARE FL DESRIKTNING H GER GT7...
Страница 34: ...34...
Страница 35: ...35...
Страница 37: ...37...
Страница 48: ...48 CONTROL DIAGRAM HERU K SHOWS ALL SENSORS FLOW DIRECTION RIGHT GT7 EXHAUST AIR EXTRACT AIR...
Страница 70: ...70...
Страница 71: ...71...
Страница 79: ...79 WIRING DIAGRAM KOPPLINGSSCHEMA 4040203 HERU 70 K A With electrical heater Med elv rmare...