16
Installation
4.1
Installation conditions
Installation position
Terminals on top and bottom
Horizontal spacing
On both sides 18 mm
Minimum vertical rail grid spacing
115 mm (90 + 25 mm)
(excluding conduit)
Recommended vertical rail grid spacing
160 mm (with 40 mm conduit)
4.2
Mounting process
The e:cue Bridge8 is designed to mount onto a 35mm DIN rail (EN 60715)
in a horizontal position.
1. Clip the device to the rail from
top.
2. Apply gentle pressure to the
top front to snap it in place. The
device has been mounted
successfully.
You can also mount the device on any flat surface. Use a 3 to 3.5mm screw
for the hanger hole.
For mechanical stability, mounting on a rail is recommended.
4.3
Ethernet connection
The pin-assignment of the Ethernet port corresponds to RJ45 standards.
You can use every common Ethernet component, like cable, splitters, and
switches. Connect the e:cue Bridge8 at the designated Ethernet interface
with a patch cable (RJ45, CAT5).
1
2
!
Ground the Ethernet cable for outdoor installations (optional
for indoor only).