9
RECOMMENDATION
- Allow clearance to the floor. Screw the feet out a minimum of 15 mm from the bottom of the
product.
-
Overflow pipe from the safety valve to the drain (1) and mains cable for wall socket (2) should be
hidden under the channels in the bottom of the product.
-
If the non-return valve is tight, a reduction valve and expansion vessel should be fitted (to stop
dripping from the safety valve).
-
If the maximum water pressure exceeds 6 bar in a 24-hour period, a reduction valve and expansion
vessel should be fitted.
-
For installation in a room which does not conform to the wetroom rules, a watertight drip tray
with overflow pipe > 18 mm inside diameter should be fitted under the product, in addition
to an automatic stop cock with sensor. This will prevent possible material damage.
3.5.5 Fitting instructions
3.5.6 Installation recommendation
!
CAUTION
!
The product should be placed in a room with a drain, and fitted in accordance with local
rules and regulations. Alternatively, fit an automatic stop valve with sensor and overflow
from safety valve to drain.
!
The product should be properly aligned vertically and horizontally, on a floor or wall suitable for
the total weight of the product when in operation. See type plate.
!
The product must have a clearance for servicing of 40 cm in front of the cover / 10 cm over the
mixer valve.
!
WARNING
!
The product should be filled with water before the power is switched on.
!
Any overflow pipe from the safety valve must be > 18 mm inside, clear, undamaged and
frost-free with a fall to the drain.