8
Product.
CW (1)
HW (2)
Overflow (4)
N 5
ø15 mm
ø15 mm
1/2" outside thread
3.5.3 Torque settings
3.5 Pipe installation
3.5.1 Incoming water pressure
The efficiency of the product depends on the in-
coming cold water pressure. The water pressure
should be min. 2 bar and max. 6 bar throughout
the day. Excessive water pressure can be adjusted
by installing a pressure reduction valve.
3.5.2 Fitting cold and hot water pipes (CW-HW),
safety valve and overflow pipe
A) Place product in the desired position. If the
product is fitted horizontally, the pipe connec-
tors must point straight up. It is recommended
that the product is secured to a wall or a suitable
surface regardless of the method chosen; use
the screw holes D, see page 7.
If the product is fitted vertically, the electric box
MUST face upwards. See pt. 3.5.7.
B) CW (1)/HW (2) fit pipes of suitable size
to the connections, tighten according to
table 3.5.3.
• For larger pipe sizes, a reducer can
be used.
C) The safety valve supplied (3) must
be fitted to the incoming CW supply pipe.
D) Any overflow pipe (5) > 1/2" inside should be
run to the overflow on the safety valve (4);
• Connect to 1/2" outside thread. Ring clamp
connector may be used (not included)
• Clear, undamaged and frost-free with
a fall to the drain.
The product is designed to be permanently con-
nected to the mains water supply. Approved pipes
of the correct size should be used for installation.
The relevant standards and regulations must be
followed.
* Fastening band for wall mounting fitted as de-
scribed in section 3.3.3. Screws for wall mounting
tightened until the insulation material starts to de-
form slightly.
The product must be fitted to a wall surface de-
signed to withstand the weight of the product in
operation.
Component
Torque
Connection to CW/HW (ø15)
40 Nm (+/- 3)
Ring clamp connection to safety valve 40 Nm (+/- 3)
Screws for mounting band
Depending on
surface*
5
5
4
3
3
1
2
3
1
2