Installation and operating manual for WATERFRIEND exclusive MRD-2 Page 20 (44)
Setting the maximum ORP metering time
The dosing time is a safety feature and prevents dangerous overdosing in case of failure. Attention! The larger the
maximum dosing time is set, the more chlorine solution can be released in an uncontrolled manner in case of any
damage to the dosing tube!
The metering time must be adapted to the actual pool size.
Procedure:
Press the "MENU" key
Move the cursor (blue backed text) to the line "set ORP" by pressing the keys
or
.
Press the
OK
key.
Press the "NEXT" key
Move the cursor (blue backed text) to the line "max. dosage time" by pressing the keys
or
.
Press the
OK
key.
You can move the cursor by pressing the arrow keys and
and also use the
and
arrow keys to set the time limit.
The maximum and minimum possible values are shown right
and left in the display.
Max. time
Press the
OK
key to save the settings.
ORP Power-on delay
The controller only starts up after a delay period once the power supply has been provided and once external
enable has been switched on (e.g. filter control unit). This power-on delay is necessary because a period specific
to the overall system elapses once the filter pumps have been switched on before the completely mixed water
reaches the sensors. This mixing process is mainly dependent on the pool size, the dimensions of the filter pump,
the pipe length and the filter itself.
The delay period can, if required, be adapted to the actual
pool size.
Procedure:
Press the "MENU" key
Move the cursor (blue backed text) to the line "set ORP" by pressing the keys
or
.
Press the
OK
key.
MIN
MAX
1
300
30
30
7,20
800
721
675
D -2%
D +10%
pH
mV
Factory setting: 60 minutes
7,20
800
721
675
D -2%
D +10%
pH
mV