Installation and operating manual for WATERFRIEND exclusive MRD-2 Page 19 (44)
Metering pump
flow rate in %
Procedure:
Press the "MENU" key
Move the cursor (blue backed text) to the line "set ORP" by pressing the keys
or
.
Press the
OK
key.
Press the "NEXT" key
Move the cursor (blue backed text) to the line "P-range" by pressing the keys
or
.
Press the
OK
key.
You can move the cursor by pressing the arrow keys and
and also use the
and
arrow keys to set the proportional
range. The maximum and minimum possible values are shown
right and left in the display.
P-range
Press the
OK
key to save the settings.
Meaning of the proportional range
Adjustment
Benefits
Disadvantages
Diagram
Narrow P-range Fast, accurate control
When switching on, an overshoot
can occur
Wide P-Range
No overshoot
Slow control, small deviations
between desired and actual
values possible
7,20
800
721
675
D -2%
D +10%
pH
mV
Factory setting: 100mV
MIN
MAX
10
200
100
100