background image

OSAKA

 - OF 33 AZ - OPERATING INSTRUCTIONS - Vr. 01 - PAG. 5

 

 
4.5  - COMPRESSOR PROTECTION FUNCTION AND DELAY 
AT POWER-ON 

All  the  parameters  concerning  the  compressor  protection 
functions and the delay at power on are contained in the group 

]

PrC”. 

The  function  “Compressor  Protection”  carried  out  by  the 
machine  aims  to  avoid  close  start  ups  of  the  compressor 
controlled by the instrument in cooling applications. 
This function foresees a time control on the switching on of the 
“Out”  output  associated  with  the  temperature  regulation 
request. 
The protection consists of preventing the output being switched 
on  during  the  time  set  in  the  parameter 

“PtC”

  and  counted 

depending  on  what  has  been  programmed  in  the  parameter 

“PSC”

,  and  therefore  that  any  activation  occurs  only  after  the 

“PtC” time has finished. 
If  during  the  power  on  delay  phase,  the  regulator  request 
should  disappear,  due  to  an  inhibition  caused  by  the 
compressor  protection  function,  the  foreseen  start  up  of  the 
output is naturally cancelled

.  

Using  the  parameter

 

"PSC",  it  is  possible  to  set  the  type  of 

compressor  protection  and  therefore  from  when  the  inhibition 
time “PtC” must start. 
The parameter “PSC”  can be set as: 

= 1

 : Power on delay 

T e m p .

O u t

P t C

o f f

O N

S P

P t C

P t C

" P S C "   =   1

t i m e

H S E t

o f f

o f f

o f f

O N

O N

P r 1

 

= 2

 : Delay after power off 

O N

O u t

o f f

P t C

P t C

P t C

S P

T e m p .

" P S C "   =   2

t im e

H S E t

O N

O N

o f f

o f f

P r 1

 

= 3

 : Delay between power on phases. 

P t C

O u t

o f f

S P

O N

T e m p .

P t C

P t C

t i m e

H S E t

" P S C "   =   3

o f f

o f f

O N

O N

P r 1

 

The function is disabled by programming “PtC” = 0. 
Through  the  parameter

 

“LCt”

  it  is  also  possible  to  set  the 

minimum  activation  time  of  the  output  to  avoid  switching  on of 
the compressor that is too short. 
During  the  power  on  delay  phases  of  the    OUT  output  by 
inhibiting  the  function  “Compressor  Protection”    or  delay  of 
power  off  caused  by  the  minimum  function  time  “LCt”,  the  led 
OUT flashes. 
It  is  also  possible  to  prevent  activation  of  all  the  outputs  after 
the  instrument  is  turned  on,  for  the  time  set  in  the  parameter 

“od”

The function is disabled by “od” = OFF. 
During  the  power  on  delay  phase,  the  display  shows  the 
indication 

od,

  alternating  with  the  normal  programmed 

visualisation. 
 

 

4.6 - DEFROST CONTROL

 

All  the  parameters  concerning  the  defrosting  control  that  acts 
on the outputs configured as “Out” and “dEF”, are container in 
the group 

]

dEF”.

 

The type of defrosting that the instrument must carry out is set 
by the parameter 

“dtyP”

 that can be programmed: 

=  EL

  -  WITH  ELECTRICAL  HEATING    or  BY  STOPPING 

COMPRESSOR  (during  defrosting,  the  output  “Out”  is 
deactivated while the output “dEF” is enabled) 

=  in

  -  WITH  HOT  GAS  or  INVERSION  OF  CYCLE  (during 

defrosting the outputs “Out” and “dEF” are enabled) 
The  automatic  defrosting  can  take  place  at  intervals  or  if  the 
instrument has an internal clock, at set hours. 
Defrosting  at  intervals  is  possible  by  setting  the  time  that  runs 
between  the  two  next  automatic  defrostings  in  the  parameter 

“dint”

Counting  this  interval  is  set  through  the  parameter 

"dCt"

  that 

can be programmed: 

= rt

 - counts the total function time (instrument on) 

=  ct

  -  counts  only  the  compressor  function  time  (output  OUT 

switched on) 

=  cS

  -  the  instrument  carries  out  a  defrosting  cycle  at  each 

compressor  stop  (i.e.  at  each  deactivation  of  the  output OUT). 
If this option is used, set “dint”=OFF. 
if the instrument has an internal clock, it is possible to carry out 
up to 6 defrostings per day at set times.  
To  use  this  mode,  it  is  necessary  to  set  the  parameter 
"dint"=OFF so that the defrosting at intervals is disabled and to 
set  the  parameters 

“dF  1”,  “dF  2”,  “dF  3”,  “dF  4”,  “dF  5”, 

“dF 6”

 with the times when the defrosting must be carried out. 

The automatic defrosting cycle can be at time intervals or, if an 
evaporator probe is used (Pr2), when a temperature is reached. 
If  the  evaporator  probe  is  not  used  (par.  “Pr  2”  =  OFF)  the 
duration cycle is set by the parameter 

“dEFE”. 

If instead the evaporator probe is used (parameter “Pr 2” = on) 
the  defrosting  takes  place  when  the temperature measured by 
the  probe  exceeds  the  temperature  set  in  the  parameter 

“tEdF”.

 

If  this  temperature  is  not  reached  in  the  time  set  in  the 
parameter “dEFE”, defrosting is interrupted. 
In  order  to avoid pointless defrosting the parameter.

 

“tSdF”

 is 

foreseen that sets the enablement temperature for defrosting 
If  the  temperature  measured  by  the  probe  is  higher  than  the 
one  set  in  the  parameter 

“tSdF”  and  in  the  parameter  "tEFE" 

the defrosting is inhibited. 

( N O   d e f . )

( d e f r o s t )

t E d F

d E F

o f f

O N

t S d F

d in t

1

P r 2

T e m p .

( d e f r o s t )

d in t

d E F E

2

d in t

d in t

3

t im e

o f f

o f f

O N

 

Examples:

  defrosting  1  ends  due  to  reaching  of  temperature 

“tEdF”, defrosting 2 ends at the end of the  “dEFE” time as the 
temperature  “tEdF”  is  not  reached,  defrosting  3  does  not  take 
plac

e as the temperature is higher than “tSdF”.

 

At the end of defrosting, it is possible to delay the new start up 
of  the  compressor  (output  “Out”)  at  the  time  set  in  parameter 

“tdCO” 

to allow the evaporator to drain. 

During  this  delay,  the  led  Def  flashes  to  indicate  the  draining 
state. 
It is also possible to prevent start up of the compressor near to 
defrosting, to avoid waste of energy. 
If  inside  the  time  set  in  the  parameter 

“COFd”

  (counted  in 

advance compared to the start up of automatic defrosting both 
at  intervals  and  by  clock),  an  activation  request  for  the  output 
“Out”  should  take  place,  this  does  not  take  place  and  it  is 
signalled by the flashing of the Out led. 

Содержание OF 33 AZ

Страница 1: ...5 PROGRAMMABLE PARAMETERS TABLE 6 PROBLEMS MAINTENANCE AND GUARANTEE 6 1 SIGNALLING 6 2 CLEANING 6 3 GUARANTEE AND REPAIRS 7 TECHNICAL DATA 7 1 ELECTRICAL DATA 7 2 MECHANICAL DATA 7 3 MECHANICAL DIMEN...

Страница 2: ...e desired parameter can be selected and pressing the Set key the display will alternately show the parameter code and its setting that can be changed with the UP and DOWN keys Once the desired value h...

Страница 3: ...lectronic devices or electromechanical safety and warning system They should be placed outside the measuring and control equipments possible protective devices responding to specific safety requiremen...

Страница 4: ...y function through a contact that is normally open and closed when the alarm sounds ALt to control a silenceable alarm device through a contact that is normally closed and then open when the alarm sou...

Страница 5: ...abled in WITH HOT GAS or INVERSION OF CYCLE during defrosting the outputs Out and dEF are enabled The automatic defrosting can take place at intervals or if the instrument has an internal clock at set...

Страница 6: ...d When the probe Pr2 is used par Pr 2 on the fans as well as being conditioned by the parameters FCOF and FEdF are also conditioned by the temperature control It is possible to set the disablement of...

Страница 7: ...zer with an alarm memory ALL or ALL it is necessary to set the parameter tAL yES 4 10 DIGITAL INPUT All the parameters concerning the digital input functions are contained in the group din The digital...

Страница 8: ...the second is disabled In this mode the AUX output can be turned off automatically after a certain time that can be set on the parameter tuA With tuA OFF the output is activated and deactivated only...

Страница 9: ...frost 2 OFF 00 00 23 59 hrs min OFF 23 dF 3 Time start defrost 3 OFF 00 00 23 59 hrs min OFF 24 dF 4 Time start defrost 4 OFF 00 00 23 59 hrs min OFF 25 dF 5 Time start defrost 5 OFF 00 00 23 59 hrs m...

Страница 10: ...dEF FAn AuS ALt AL ALL ALt AL ALL Out 61 Out2 Configuration of output function OUT2 see Out1 OFF Out dEF FAn AuS ALt AL ALL ALt AL ALL dEF 62 Out3 Configuration of output function OUT3 see Out1 OFF Ou...

Страница 11: ...250 VAC and OUT3 SPST NO 5A AC1 2A AC3 250 VAC 16 A Max for common pin 1 Electrical life for relay outputs 100000 operat VDE om Installation category II Measurement category I Protection class against...

Отзывы: