Osaka F 10 Скачать руководство пользователя страница 5

Osaka

 - 

F 10

 - User Manual - V1 - PAG. 5

4.2.1 

Electrical wiring diagram

Supply

1

3

2

4

6

5

7

9

8

10

12

11

SPST-NO

INPUTS

OUT

(12 A max. for extr. conn. model)

Pr1

Digital
Input

Pr2

16 FLA

96 LRA

15 A Res.

EN

30 (15) A

61810

Out (H):

15 (15) A

5 FLA

30 LRA

12 A Res.

16 (9) A

Out (R):

10 (4) A

60730

EN

UL

5. FUNCTIONS

5.1 ON/Stand-by 

function

Once powered the instrument can assume 2 different condi-

tions:

ON

:  Means that the controller uses the control functions.

STAND-BY: 

Means that the controller uses no control function and 

the display is turned off except for the Stand-by LED.

The transition between Standby and ON is equivalent to power 

ON the instrument providing the electrical power

In case of power failure, the system always sets itself in the 

condition it was in before the black-out

The ON/Stand-by function can be selected:

 

– With the key   pressed for 1 s if tUF = 3;

 

– With the key   pressed for 1 s if tfb = 3;

 

– Using the Digital Input if parameter iFi = 7;

5.2  Normal and economic operation

This tool allows to pre-set two different Setpoints, one 

Normal

 

SP

 and one 

Economic

 - 

SPE

.

Associated with each Setpoint there is the relative differential 

(hysteresis): 

Normal

 - 

rd

 and 

Economic

 - 

rEd

.

Switching between the two modes can be 

automatic

 or 

manual

.

5.2.1 

Normal/Economic operation selection

This function can be used when you need to switch two functional 

temperatures (eg. Day/Night or week-day/week-end).  The Normal/

Economic operation can be selected in manual mode:

 

– Using the   key if parameter tUF = 2;

 

– Using the   key if parameter tFb = 2;

 

– Using the Digital Input if parameter iFi = 6.

The Normal/Economic operation can be selected in automatic 

mode:

 

– Elapsed the iEt time after the door has been closed 

(Normal/Eco switching).

 

– At door opening if the SPE Setpoint is activated by iEt pa-

rameter (Eco/Normal switching).

 

– Elapsed the itt time after the door has been closed and from 

the activation of SPE Setpoint by iEt parameter (Eco/Normal 

switching).

To use this function, it is necessary to set the Digital Input as: 

iFi

 = 

1

2

 or 

3

.

If 

iEt

 = 

oF

 the selection of Eco/Normal modes via the digital 

input is disabled.

If 

itt

 = 

oF

 the time-out switching from Eco to Normal mode is 

disabled.

Switching to Economic mode is indicated by the label 

Eco

.  

When 

idS

 = 

Ec

 the Economic mode is pointed out with a fixed 

Eco

 label otherwise the label 

Eco

 appears every 10 s alter-

nated to the display set with parameter 

idS

.

The normal Set Point 

SP

 can be set to a value between the one 

set with parameter 

SLS

 and the one set with parameter 

SHS

 

while the Economic Set Point 

SPE

 can be set to a value between 

the one set with parameter 

SP

 and the one set with parameter 

SHS

.

Temp.
Pr1

SPE

SP

Door

rd

rEd

iEt

time

“Norm.”

DAY (Shop open)

DAY (Shop open)

NIGH (Shop closed)

“Norm.”

“ECO”

Note: 

In the following examples the Set point is generally 

indicated as 

SP

 and the differential as 

rd

 however the 

instrument will act according to the Set Point and the dif-

ferential selected as active.

5.3  Measure and display configuration

With the 

iuP

 it is possible to select the temperature engi-

neering unit and the desired measure resolution (

C0

 = °C/1°; 

C1 

= °C/0.1°; 

F0

 = °F/1°; 

F1

 = °F/0.1°).

The instrument allows the measure calibration, which can be 

used to recalibrate the instrument according to application 

needs, The calibration is made by using parameters 

iC1

 (input 

Pr1) and 

iC2

 (Pr2 input).

Parameter 

iP2

 allows to select the instrument usage of Pr2 

measure as:

Au

 Auxiliary 

probe;

DG

  Digital Input (see the Digital input functions).

If 

Pr2

 input is not used, set 

iP2

 = 

oF

.

Using 

iFt

 parameter can be set a software filter for the measur-

ing the input values in order to decrease the sensibility to rapid 

temperature changes (increasing the sampling time).  Through the 

idS

 parameter is possible to set the variable normally displayed:

P1: Pr1 

probe measurement;

P2: Pr2 

probe measurement;

SP: 

Active Set Point;

EC:

  Probe measure if the instrument is in Normal Mode, the 

label 

Eco

 if the instrument is in (

Eco mode

);

OFF: 

If the numerical display must be switched off (

oF

).

When is displayed one of the measures 

idS

 = 

P1

/

P2

/

Ec

 the 

iCU

 

parameter allows to set an offset that is to be applied only to the 

displayed variable (all controls will always happen according to 

the correct temperature value, changed only by the calibration 

parameters).

Regardless of what is set at 

idS

 parameter, all the measure-

ment variables can be shown pressing the   key.

The display alternately shows the code that identifies the vari-

able (see below) and its value.  The variables are:

Pr1

  Probe 1 measurement;

Pr2

  Probe 2 measurement (on/oFF if Pr2 is a Digital input);

Lt

 

Minimum stored Pr1 temperature;

Ht

 

Maximum stored Pr1 temperature.

Содержание F 10

Страница 1: ...ay output and 2 NTC temperature probes inputs one of which can be configured as digital input it can also be equipped with a built in buzzer for acoustic report of the alarms Index 1 Instrument descri...

Страница 2: ...rogramming The normal mode to program the setpoint is done by momen tarily pressing the set key the display shows SP or SPE alter nated to the programmed value To change it press the key to increase t...

Страница 3: ...ameters then the r p parameter through which will be pos sible to access the protected parameters Normal mode 2 s 5 s Increase value Decrease value 25 5 25 5 r p r p Previous Param Not protected param...

Страница 4: ...ouse devices which may overheat or which may cause the instrument to function at a higher tem perature than the one permitted and declared Connect the instrument as far away as possible from sources o...

Страница 5: ...When idS Ec the Economic mode is pointed out with a fixed Eco label otherwise the label Eco appears every 10 s alter nated to the display set with parameter idS The normal Set Point SP can be set to...

Страница 6: ...above but obtained through a NC contact and a reversed logic operation 5 5 Temperature control The instrument control is ON OFF and acts on the output depend ing on the PR1 probe measuring the Set Po...

Страница 7: ...on parameter AdA ddL oF The display continues showing the temperature meas ured by the Pr1 probe during the defrost cycle 5 8 Alarm functions The alarm conditions of the instrument are Probe errors E...

Страница 8: ...eys in addition to their normal functions can be configured to operate other commands The key func tion can be defined using the tUF parameter while the key via parameter TFb Both parameters have the...

Страница 9: ...defrosting is allowed 99 9 999 C F 2 0 23 dtF Temperature that forces the beginning of the de frosting 99 9 999 C F 99 9 24 dSt Delay in the beginning of a defrosting because of evaporator probe oF Di...

Страница 10: ...to perform the necessary steps Request document repair RMA by mail or fax and complete it is necessary send the RMA and the device to SAT OSAKA by method prepaid 7 4 Disposal The appliance or the prod...

Страница 11: ...5 fs 1 digit Sampling rate 130 ms Display 3 Digit Red or Blue optional height 17 7 mm Software class and structure Class A Compliance Directive 2004 108 CE EN55022 class B EN61000 4 2 8kV air 4kV cont...

Отзывы: