INSTALLATION GUIDE

Instruction Manual

1-888-543-6473
1-888-541-6474

13376 Comber Way 

Surrey BC V3W 5V9

[email protected] 
www.ortechindustries.com

375 Admiral Blvd

 

Missis

s

auga

ON L5T 2N1

LED Emergency Lights

MODEL

 

O

E-21

6-72W

Operation

1.

To test, depress the TEST switch. Charge indicator will go out and the DC lamps will come on

2.

Release the TEST switch. DC lamps will be extinguished, and the charge indicator will come on

3.

A bright charge LED indicator light indicates a high charge rate. After the battery has reached full charge, the indicator light
will go out. Under normal operation, the high charge indicator will turn ON and OFF intermittently while the unit is in
standby mode (regular AC is present) since the charge rate will vary in order to maintain an optimal battery performance

Fig.6

Fig.

7

OPERATION AND MAINTENANCE

Maintenance

1. Code requires that the equipment be tested every 30 days for 30 seconds, and that written records be maintained for all

test results and repairs. Furthermore, the equipment is to be tested once a year for the required duration as per Code.
The battery is to be replaced or the equipment repaired whenever the eqeuipment fails to operate as intended during the
duration test. The manufacturer strongly recommends compliance with all Code requirements

2. Clean lenses on a regular basis to provide maximum light distribution in case of an emergency.

NOTE — The servicing of any parts should be performed by qualified service personnel ONLY. The use of replacement
parts not furnished by the manufacturer may cause equipment failure and will void the warranty

Emergency Lamps do not come on at all:

Pilot Light is out before test...

1.

Check AC supply — be sure unit has 

3

0 hour AC supply (un-switched)

2.

AC supply is OK, and indicator light is out, replace PC Board Assembly. Pilot Light is on before test

3.

Either the output is shortened or overloaded, or the battery is not connected

4.

Battery is severely discharged. Allow 

3

0 hours for recharge and then retest. NOTE — This could be the result of a switched

AC supply to the unit (which has been turned OFF at some point), a battery with a shortened cell, an old battery or a
battery which has been discharged due to a long power outage and is not yet fully recharged

TROUBLESHOOTING

Содержание OE-216-72W

Страница 1: ...horized personnel will not readily subject it to tampering 3 The use of accessory equipment not recommended by manufacturer may cause an unsafe condition and will void the unit s warranty 4 DO NOT use this LED Emergency Light for other than its intended purpose 5 Failure to insulate unused wire may result in shock hazard or unsafe condition as well as equipment failure Hardwire Installation 1 Exte...

Страница 2: ...led in the cabinet must be connected to the circuit board see Wiring Diagram on page 1 and Fig 2 9 Secure all internal wires 10 Replace cover and secure cover screws 11 Turn on AC line voltage supply 12 If the unit is supplied with a line cord connect the line cord plug into the appropriate receptacle previously installed 13 If unit is complete with lamp heads position the lamp heads to provide be...

Страница 3: ...e tested once a year for the required duration as per Code The battery is to be replaced or the equipment repaired whenever the eqeuipment fails to operate as intended during the duration test The manufacturer strongly recommends compliance with all Code requirements 2 Clean lenses on a regular basis to provide maximum light distribution in case of an emergency NOTE The servicing of any parts shou...

Страница 4: ...gency Lamps come on dim when AC power is ON 1 Check supply voltage and AC connections This emergency light is provided with brownout protection The AC supply must be at least 80 of nominal 120V on a 347V line for equipment to function normally 2 At lower voltages the emergency lamps will begin to glow dimly until the source voltage drops below the full turn on point NOTE This condition may also be...

Отзывы: