MANUAL MODE

 allows you to keep your fan at a constant speed

 

level, regardless of the current room temperature

MANUAL MODE

 is indicated with the 

HAND

 icon in the top 

centre

 

section of the screen

To select your desired speed level, press the 

UP

 or 

DOWN 

arrow

 

buttons on the controller

You can select between 6 speed levels, which correspond to the

 

following percentages from the maximum fan motor output:
- Level 0 corresponds to the output of 0% from the max. speed
- Level 1 corresponds to the output of 15% from the max. speed
- Level 2 corresponds to the output of 32% from the max. speed
- Level 3 corresponds to the output of 50% from the max. speed
- Level 4 corresponds to the output of 67% from the max. speed
- Level 5 corresponds to the output of 83% from the max. speed
- Level 6 corresponds to the output of 100% from the max. speed

The selected speed level is indicated on the controller's screen by

 

the rotating impeller icon and the number between 0-6

.

AUTO MODE

 allows the controller to automatically adjust the 

speed of the connected fans to maintain your pre-determined target 
temperature (based of the temperature reading of the 
thermal probe).

To set up 

AUTO MODE

, ensure that the 

AUTO

 icon is displayed in the 

centre of the top row of the controller's screen. If you see the 

HAND

 

icon instead, press and hold the 

MODE

 button for 3 seconds until the 

icon switches to 

AUTO

Use the 

UP

 and 

DOWN

 arrows to select the desired temperature. 

This temperature represents the level that you want to maintain in 
your ventilated space. The desired temperature can be selected from 
0ºC (32ºF) up to 60ºC (140ºF).

Programmable Auto Mode

Auto Mode Baseline Speed

BASELINE (DEFAULT)

 speed level is the speed level maintained 

by the controller when your desired temperature has 
been reached

Select the 

BASELINE

 speed level by pressing the 

MODE

 button 

once again when 

AUTO MODE

 is already activated. The number 

displayed under the spinning propeller icon will start blinking, 
allowing you to select a value from 0 to 6.

In applications which require moving air even when your target 
temperature is reached, we recommend the 

BASELINE

 speed be 

set at level 1-3, so that the fan maintains low to medium airflow 
while the temperature is already at your desired level

If your application requires the fan to be turned off when your 
target temperature has been reached, the 

BASELINE

 speed must 

be set at level 0. This effectively means that you want the fan to 
be blowing only when the temperature in your ventilated space 
exceeds your target level.

Auto Mode 

Speed Adjustment Logic

When the room temperature increases over your desired level, the 
controller will automatically accelerate the speed of all connected 
fans to reduce the temperature to your desired level.

The fan's speed will increase by 1 additional speed level for every 
2ºC/2ºF difference over your desired temperature level.

In the scenario when your desired temperature level selected for 

AUTO MODE

 is 30°C and your baseline speed level is 1. Once the 

room temperature increases to 32°C, the fan's speed will increase to 
level 2. If the temperature increases to 34°C, the fan's speed will 
increase to level 3 and so on until the fan's speed reaches level 6 at 
40°C or above.

The fan speed will decrease by 1 speed level for each 2ºC/2ºF 
reduction in difference over your desired temperature level.

Temperature Alarm

TEMPERATURE ALARM

 feature allows the user to select the 

temperature level, which once reached, triggers the fan to 
immediately accelerate to the maximum speed.

The fan will override the current speed setting and blow at 
maximum speed until the temperature reduces below the 

TEMPERATURE ALARM

 level or unless the 

TEMPERATURE 

ALARM

 is deactivated by the user.