GENERAL INSTRUCTIONS FOR CTC
UNDER POLE COMPACT
TRANSFORMER SUBSTATION
IG-086-GB
version 02
11.07.2007
Page 17 of 20
If the transformer is fitted with open porcelain bushings, as per the standard UNE-EN 50180,
it is recommended to make the connection to the M12 bolt of the bushing with the connecting
points.
3.8.2. Connection between the Transformer and the LVB
It is recommended to make the connection between the transformer and the LVB with
0.6/1 kV extraflexible copper wire of adequate cross-section with hexagonal connectors, as
per DIN 46.235.
The connection is made directly on the busbar with M10 screws
[4]
.
3.8.3. Connection of the Cables to the LVB Outgoing
The LV cable outgoings are made with the LVB’s BTVC bases screws.
[4]
To identify the phases, pay attention to the colour code on the cables and on the bars.