Page 10 of 20
GENERAL INSTRUCTIONS FOR CTC
UNDER POLE COMPACT
TRANSFORMER SUBSTATION
IG-086-GB
version 02
11.07.2007
3.4. DIMENSIONS OF THE EXCAVATION
It is recommended to make an excavation for the installation, as shown in Figure 3.3.
The burying level marked on the
CTC
TS walls must not be exceeded. The maximum
burying height is 480 mm measured from the base of the Transformer Substation.
These levels will be adapted to the earth network solution taken for each case, according to
the earth connection guide plan
[3]
.
[3]
Necessary excavation for the recommended earthing ring: see Figure 3.9.
ORMAZABAL
LECHO DE ARENA COMPACTADA DE
1770
2550
480
100 mm compacted sand
Dimensions in millimeters
Figure 3.3
:
Dimensions of the excavation
2550
1770
480