34
Maintenance Intervals of the Main Parts
Approximate interval time when it becomes necessary to replace the parts depending on conditions of use
Approximate interval time when it becomes necessary to replace the
parts depending on conditions of use
Part number
Part name
Qty/product
Remarks
Replacement time
1 0A002056000
Compressor
1
RKS400F-S
20,000Hr
2 0A000922010
RKS500F
3 0A000385020
RKS750F
4 0A000673010
Fan motor
RKS400F-S
5 0A000736000
RKS500F
6 0A000579000
RKS750F
7 03A30650010
Pump
RKS400F-S
8 03A30649010
RKS500F
9 03A30746010
RKS750F
10 0A000914000 Evaporating
pressure
regulator
RKS400F-S,750F
11 0A000968000
RKS500F
※
The indicated interval time is the time when the possibility of reaching the wear failure occurrence
range becomes higher. Since the aforementioned interval time may defer depending on the installation
environment, it may not be always necessary to replace the subject parts when the interval time has
come. However, after the replacement time passed, and there is a failure when checking, replace or
repair the subject parts.
※
Times assume the operating condition of 10 hours/day or 2,500 hours / year without frequent starts
and stops (referring to the industrial air conditioner standard defined by the Japan Refrigeration And
Air Conditioning Industry Association)
Содержание RKS400F-S