- 8 - 

 

 

Installation and use manual for OT-U250PP & OT-U500PP 

 

INPUT SIGNALS 

9.1.2.

A

 By connecting this input to positive, FOGGING SYSTEM is armed, blue frontal LED is switched on and 

when the machine reaches proper temperature it means that it is ready for shooting. 

In case of alarm, opening ARM input, the fog emission stops immediately, even if the time set wasn’t 

reached. 

S

 Putting this input to positive, if FOGGING SYSTEM is hot and armed, starts fog emission for the set time 

(see paragraph 12). 

 

 

VALIDATION INPUT 

9.1.3.
In order to validate this input, it’s necessary to insert the jumper W4. This input automatically generates 

AND function with input S. 

If any input receives the shooting command, the generator doesn’t emit fog if within 1 minute doesn’t 

receive the command also from the second input. 

P+ Output

 positive to give power to a validation sensor or a remote control receiver, max 300 mA. 

P- Output

 negative to give power to a validation sensor or a remote control receiver, max 300 mA. 

PV

 Validation input. It’s possible to connect to this input a validation sensor with a contact normally closed 

connected to the terminal P-. 

In order to check the correct operation of PV input, it’s necessary to remove the jumper W4. 

When AND function is disabled, to each opening of PV input you will hear a “beep” for 5’’. At the end of the 

test, re-establish AND function inserting jumper W4 again 

 

 

OUTPUTS 

9.2.

E

 This output (NPN Open Collector) closes towards negative direction when the bag is empty. This output 

(NPN open collector) closes towards negative when the fogging machine emitted fog for at least 100’’ or 

when the bag is empty. The signal is activated by a sensor that detects the absence of liquid just while 

shooting. 

The empty bag signal is deactivated only making the RESET (see paragraph 14). For this reasons, if the bag is 

not inserted, or there is an empty bag inside, FOGGING SYSTEM will detect it just after a shot. 

F

 This output (NPN Open Collector) closes towards negative when there is a malfunction (such as batteries 

expired, fault of power supply or temperature control fault), which compromises the functioning of the 

device and which requires a technical action. 

This output (NPN Open Collector) closes towards negative direction when you open the bag door or 

when the accelerometer detects a sudden movement (such as the detachment from the wall). 

C

 This output (NPN open collector) closes towards negative only after that the system has emitted fog for 

the set time. If the emission of fog is interrupted (if there is an interruption of ARM command, if the glycol 

finishes, if there is not thermal autonomy anymore) this output will not change its status. 

 

Remember, it is necessary to connect all three outputs to an alarm central or an electronic 

panel that can see all those information in real time and take proper action. 

In order to avoid accidental activation with subsequent fog emission, the inputs are in 

“negative security”, for this reason the disconnection of a wire does not cause activation. 

So it is necessary to check carefully the reliability of connections and protect the cables to the control panel 

to avoid the risk of accidental damages. 

 

 

 

Содержание OT-U250PP

Страница 1: ...Installation and use manual for OT U250PP OT U500PP...

Страница 2: ...system 9 10 1 Example of connection of inputs to an alarm with relay outputs 9 10 2 Example of connection of inputs with outputs of an alarm with open collector outputs 10 10 3 Example of connection...

Страница 3: ...on glycol water and alcohol Any employee or worker that may be exposed to fog must be warned in advance and must be checked for any allergy to the substances listed above At the date of printing of th...

Страница 4: ...maximum shown in the shooting table avoid overshooting even if the produced fog is dry and generally doesn t leave residue A shot that goes far beyond the recommended seconds can create a residue prob...

Страница 5: ...n a flat surface The optional bracket mainly recommended for ceiling installation can also simplify standard installation by allowing to use back holes for the passage of cables Remember to use the fi...

Страница 6: ...h features before proceeding with the connection The max current to be considered for the system is 4A The connection to the 230V electricity grid must be performed by a qualified technician Connect t...

Страница 7: ...older battery not included Description of input and output connections 9 INPUTS 9 1 12V Power input 9 1 1 In these inputs is necessary to provide a stable supply between 11V and 14V DC from the alarm...

Страница 8: ...s empty This output NPN open collector closes towards negative when the fogging machine emitted fog for at least 100 or when the bag is empty The signal is activated by a sensor that detects the absen...

Страница 9: ...connection of outputs with anti robbery connection Example of connection of inputs with outputs of a standard alarm system 10 1 In the diagram above the control panel as example provides to Orion Fogg...

Страница 10: ...plest action to take is to use 2 relays to create a connection similar to the one shown in the previous diagram Example of connection of outputs to drive LEDS and or relays 10 4 In case of an empty ba...

Страница 11: ...power supply The outputs are normally opened and connected with input zones of the alarm control panel normally opened Example of connection of outputs with balanced inputs of an antitheft 10 6 In thi...

Страница 12: ...of front LEDS 11 LED BLUE When ON it means the machine is armed and if hot it s ready to shoot Flashing means something is wrong LED RED It is ON when the bag is empty LED GREEN Flashing means the he...

Страница 13: ...ht in the target area the shooting time can be increased or decreased accordingly by referring to the following formula HxLxP x D x V x I HxLxP Height x Width x Depth of the area to protect D Density...

Страница 14: ...n Higher levels of fog over suggested limits may fill the room and leave a residue Any residue usually goes away by itself within 24 48 hours otherwise being soluble in water it is enough to use a wet...

Страница 15: ...was easier to go near the machine and obstruct the nozzle After 15 minutes the compressor will stop automatically If the system is disarmed and armed again the cycle will start again for 15 minutes Af...

Страница 16: ...ew seconds when the pump for nozzle tamper control is turned on as the nozzle temperature rises rapidly reaching temperatures that may cause serious burns The air coming out of the nozzle exceeds 200...

Страница 17: ...r will monitor the nozzle After this time it will deactivate automatically if the fogging system is disarmed the compressor will go on with it reaches 15 minutes If the machine is disarmed and then ar...

Страница 18: ...tial difference or a fault In large size plants or with more than on fogging system connected with the same central in rare situations it may occur that there are potential differences between the equ...

Страница 19: ...f the machine Not included in the warranty moving parts and or damages depending on the incorrect use unless it is found a manufacturing defect in origin Liquid and bags are not covered by warranty BY...

Отзывы: