CONTROLS -
AUTHORISED USER CODE: 2244
Some keys will only be operational at the repeater after entering the authorised user code. If the operation of a switch is only available
after successfully entering the authorised user code, it will be clearly stated in this manual that these functions are only active at Access
Level 2.
NOTE:
If active please SILENCE INTERNAL BUZZER before entering code.
The four numbered keys are used to enter digits from 1 to 4 for authorised user code entry.
BUZZER SILENCE (1) – At Access Level 1 this button is used to silence the panel's internal buzzer. Access Level 2 used to confirm/accept
changes in programming.
RESET (2) – Press this button to reset the panel at Access Level 2.
LAMP TEST (3) – Press this button at Access Level 1 or 2 to test all LED indicators and the panel's internal buzzer.
Release when test is finished.
SOUNDERS (4) – Press once to activate/silence sounders. If sounders are active, for example, during a FIRE condition or in the event of
an Evacuation action, pressing this button will stop the sounders. Auxiliary Relays are not affected by this action. When selected the
disablements in Level 2, this button is used to choose the desired disablement.
ADDRESSING THE PANEL
There can be connected up to four ORION MINI- REP V2 to the ORION Conventional Panel.
When more than one Repeater is needed, each repeater has to be addressed.
To address the ORION MINI-REP V2 please follow the steps below:
1. Install and connect the repeater (refer to INSTALLATION section of this manual).
2. Apply supply voltage to main panel.
3. On the repeater, introduce code 4321 (Engineering Functions code).
4. Push OUTPUTS AUXILIARY button on the DISABLEMENTS section.
The LEDs in the FAULTS section will flash alternately (see image on the right) indicating that
the repeater is in ADDRESSING MODE. General FAULT LED on the STATUS section will flash
indicating that the communication between the Repeater and the main panel was lost.
5. Select the desired Address by pressing the Red Switch (4) consecutively until the Yellow
(FAULT) LED that corresponds to the desired Address is ON (please refer to the table below
for additional details).
6. Confirm the selection by pressing GREEN (1) key. Upon confirmation, the Red (FIRE) LED will
be activated. Remove selection by pressing the GREEN key again.
The corresponding LED will be switched OFF.
7. Exit function pressing OUTPUTS AUXILIARY button.
8. RESET the repeater by pressing the RESET key.
9. Repeat steps 3 to 8 to the remaining repeaters.
10. Reset the main panel.
Address Configuration Table
Active RED LEDs
during setup
ALL LEDS
OFF
Z1
Z2
Z3
Z4
Z5
Z6
Z7
Z8
Corresponding Address
No Address
1
2
3
4
-
-
-
-
ORION MINI-REP V2 / Installation, Operation & Maintenance Manual / © GFE 210609
6