CONTROLS -

AUTHORISED USER CODE: 2244

Some keys will only be operational at the repeater after entering the authorised user code. If the operation of a switch is only available
after successfully entering the authorised user code, it will be clearly stated in this manual that these functions are only active at Access
Level 2.

NOTE:

If active please SILENCE INTERNAL BUZZER before entering code.

The four numbered keys are used to enter digits from 1 to 4 for authorised user code entry.

BUZZER SILENCE (1) – At Access Level 1 this button is used to silence the panel's internal buzzer. Access Level 2 used to confirm/accept
changes in programming.

RESET (2) – Press this button to reset the panel at Access Level 2.

LAMP TEST (3) – Press this button at Access Level 1 or 2 to test all LED indicators and the panel's internal buzzer.
Release when test is finished.

SOUNDERS (4) – Press once to activate/silence sounders. If sounders are active, for example, during a FIRE condition or in the event of
an Evacuation action, pressing this button will stop the sounders. Auxiliary Relays are not affected by this action. When selected the
disablements in Level 2, this button is used to choose the desired disablement.

ADDRESSING THE PANEL

There can be connected up to four ORION MINI- REP V2 to the ORION Conventional Panel.
When more than one Repeater is needed, each repeater has to be addressed.
To address the ORION MINI-REP V2 please follow the steps below:

1. Install and connect the repeater (refer to INSTALLATION section of this manual).
2. Apply supply voltage to main panel.
3. On the repeater, introduce code 4321 (Engineering Functions code).
4. Push OUTPUTS AUXILIARY button on the DISABLEMENTS section.

The LEDs in the FAULTS section will flash alternately (see image on the right) indicating that
the repeater is in ADDRESSING MODE. General FAULT LED on the STATUS section will flash
indicating that the communication between the Repeater and the main panel was lost.

5. Select the desired Address by pressing the Red Switch (4) consecutively until the Yellow

(FAULT) LED that corresponds to the desired Address is ON (please refer to the table below
for additional details).

6. Confirm the selection by pressing GREEN (1) key. Upon confirmation, the Red (FIRE) LED will

be activated. Remove selection by pressing the GREEN key again.
The corresponding LED will be switched OFF.

7. Exit function pressing OUTPUTS AUXILIARY button.
8. RESET the repeater by pressing the RESET key.
9. Repeat steps 3 to 8 to the remaining repeaters.
10. Reset the main panel.

Address Configuration Table

Active RED LEDs

during setup

ALL LEDS

OFF

Z1

Z2

Z3

Z4

Z5

Z6

Z7

Z8

Corresponding Address

No Address

1

2

3

4

-

-

-

-

ORION MINI-REP V2 / Installation, Operation & Maintenance Manual / © GFE 210609

6

Содержание MINI-REP V2

Страница 1: ...rconnecting technologies RS232 RS485 Fiber Optics and TCP IP options are under development The unit is provided as standard with an RS232 interface Power for the ORION MINI REP V2 can be supplied from the control panel s auxiliary power output or from an external 24 Volt DC power supply if required IMPORTANT SAFETY NOTES This equipment must only be installed and maintained by a suitably qualified ...

Страница 2: ...onnections should be performed with all elements of the Fire Detection System unpowered The Repeater should be located where access to the internal components is not restricted and where the unit is not exposed to high levels of moisture vibration and shock WARNING Observe ESD precautions when handling the PCBs All cables should be screened WARNING Cable screen s should only be connected at one po...

Страница 3: ...CONNECTION DIAGRAMS ORION MINI REP V2 General hardware and connections layout ORION MINI REP V2 Installation Operation Maintenance Manual GFE 210609 3 ...

Страница 4: ...ween Panel ORION MINI REP should be 100 meters ORION MINI REP V2 RS 485 interface Multi repeater connection until a maximum of 4 NOTE If more than one Repeater is connected in order for them to work properly some configurations are needed Please refer to the ADDRESSING THE PANEL section in this manual ORION MINI REP V2 Installation Operation Maintenance Manual GFE 210609 4 ...

Страница 5: ...panel firmware FAULTS SUPPLY FAULT This LED will be ON whenever the Main Supply has been removed or has dropped below 20 Volts BATTERY FAULT Indicates that there is low voltage level on the batteries or the battery charger circuit has failed AUX SUPPLY FAULT Indicates that the Auxiliary Supply has a fault EARTH FAULT When this indicator is ON there is leakage current flowing between the Earth conn...

Страница 6: ...EP V2 to the ORION Conventional Panel When more than one Repeater is needed each repeater has to be addressed To address the ORION MINI REP V2 please follow the steps below 1 Install and connect the repeater refer to INSTALLATION section of this manual 2 Apply supply voltage to main panel 3 On the repeater introduce code 4321 Engineering Functions code 4 Push OUTPUTS AUXILIARY button on the DISABL...

Страница 7: ...ndensing OPERATING TEMPERATURE 10ºC to 50ºC DIMENSIONS 256 L x 194 W x 75 H mm WEIGHT 1 4 Kg COLOUR CASE MATERIAL White or Red ABS GLOBAL FIRE EQUIPMENT S A Sítio dos Barrabés Armazém Nave Y Caixa Postal 908 Z 8150 016 São Brás de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire equipment com Technical Support techs globalfire equipment com www globalfire equipment com ORION MINI REP V...