PANEL STATUS INDICATORS & CONTROLS

STATUS

FIRE – LED used to indicate any FIRE ALARM condition present on panel.

FAULT – LED used to indicate Fault condition present on panel. In case of communication fault between ORION and ORION MINI REP V2
or any other peripheral, Fault LED will flash at a rate of once per second.

DISABLED – Disabled Status LED used to indicate that the panel has functions that have been disabled in either Access Level 2 or 3
modes. Check ORION for detailed information.

TEST – This LED is active whenever panel is in TEST MODE. Only activated when in Engineering Mode and TEST mode has been selected
at the ORION panel.

SUPPLY - This LED signals the presence of Supply. Additionally, when in Access Level 1 this LED is permanently on. If in Access Level 2
(USER CODE 2244) this LED will flash at a rate of once per second.

SYSTEM FAULT – This LED will be lit whenever there is a processor failure or corruption of the panel firmware.

FAULTS

SUPPLY FAULT – This LED will be ON whenever the Main Supply has been removed or has dropped below 20 Volts.

BATTERY FAULT – Indicates that there is low voltage level on the batteries or the battery charger circuit has failed.

AUX. SUPPLY FAULT – Indicates that the Auxiliary Supply has a fault.

EARTH FAULT – When this indicator is ON, there is leakage current flowing between the Earth connection/wiring and any other wire
connected to the panel.

SOUNDER FAULT 

If there is a conventional sounder circuit fault, the general FAULT LED will be lit and the DISABLE SOUNDERS LED in

the DISABLEMENTS section will be flashing.

ZONES & INPUTS

Individual zone and monitored input indicators are provided for both FIRE/ALARM, EXTINGUISH and FAULT conditions. If any of these
inputs is disabled, then its Fault LED will also be used to indicate the disablement of that particular zone/ input. The zone/ Input
Disabled LED will be ON along with the associated disabled status LED. Flashing Fault LED along with general Fault LED indicates fault on
that zone.

ORION MINI-REP V2 / Installation, Operation & Maintenance Manual / © GFE 210609

5

Содержание MINI-REP V2

Страница 1: ...rconnecting technologies RS232 RS485 Fiber Optics and TCP IP options are under development The unit is provided as standard with an RS232 interface Power for the ORION MINI REP V2 can be supplied from the control panel s auxiliary power output or from an external 24 Volt DC power supply if required IMPORTANT SAFETY NOTES This equipment must only be installed and maintained by a suitably qualified ...

Страница 2: ...onnections should be performed with all elements of the Fire Detection System unpowered The Repeater should be located where access to the internal components is not restricted and where the unit is not exposed to high levels of moisture vibration and shock WARNING Observe ESD precautions when handling the PCBs All cables should be screened WARNING Cable screen s should only be connected at one po...

Страница 3: ...CONNECTION DIAGRAMS ORION MINI REP V2 General hardware and connections layout ORION MINI REP V2 Installation Operation Maintenance Manual GFE 210609 3 ...

Страница 4: ...ween Panel ORION MINI REP should be 100 meters ORION MINI REP V2 RS 485 interface Multi repeater connection until a maximum of 4 NOTE If more than one Repeater is connected in order for them to work properly some configurations are needed Please refer to the ADDRESSING THE PANEL section in this manual ORION MINI REP V2 Installation Operation Maintenance Manual GFE 210609 4 ...

Страница 5: ...panel firmware FAULTS SUPPLY FAULT This LED will be ON whenever the Main Supply has been removed or has dropped below 20 Volts BATTERY FAULT Indicates that there is low voltage level on the batteries or the battery charger circuit has failed AUX SUPPLY FAULT Indicates that the Auxiliary Supply has a fault EARTH FAULT When this indicator is ON there is leakage current flowing between the Earth conn...

Страница 6: ...EP V2 to the ORION Conventional Panel When more than one Repeater is needed each repeater has to be addressed To address the ORION MINI REP V2 please follow the steps below 1 Install and connect the repeater refer to INSTALLATION section of this manual 2 Apply supply voltage to main panel 3 On the repeater introduce code 4321 Engineering Functions code 4 Push OUTPUTS AUXILIARY button on the DISABL...

Страница 7: ...ndensing OPERATING TEMPERATURE 10ºC to 50ºC DIMENSIONS 256 L x 194 W x 75 H mm WEIGHT 1 4 Kg COLOUR CASE MATERIAL White or Red ABS GLOBAL FIRE EQUIPMENT S A Sítio dos Barrabés Armazém Nave Y Caixa Postal 908 Z 8150 016 São Brás de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire equipment com Technical Support techs globalfire equipment com www globalfire equipment com ORION MINI REP V...

Отзывы: