Installation Instructions
©2017 Orion Energy Systems, Inc. All rights reserved. Orion and Light Years Ahead are trademarks/
service marks of Orion Energy Systems, Inc. Design modification rights reserved. 20180108
O ri o n E n e rgy Sy s te m s , I n c .
orionlighting.com
1. 8 0 0 . 6 6 0 . 9 3 4 0
Use this instruction to install a fixture wireguard in the
field for the HBHS1 product series.
Components
1
HBHS1 Series Fixture (ordered separately)
2
LED-HBHS-WG04-KIT-SP or LED-HBHS-WG04-KIT
NOTE: Kit includes: 2 Fixture wireguards, hardware
(4 bolts, 4 nuts, 4 wireguard mounting plates, 4
screws) (See Fig. A for provided hardware)
Tools Required for Installation
-Cordless Drill with deep well socket
attachment
Step-by-Step Instructions
HBHS1 G1/GA/H1/HA/I1 Fixture Wireguard Field Installation
Instruction Number: P-INT-X-406
1
Unpack components.
2
If fixture does not have a lens installed, move
to Step 2. If fixture has a lens installed, remove
end cap screws. (See Fig. 1)
3
Place wireguard mounting plate on end of
the fixture. If fixture has a lens installed,
use screws from Step 1 to attach wireguard
mounting plate in place. If fixture does not have
a lens installed, use the screws provided in the
hardware kit (See Fig. 2)
4
Repeat Step 3 for the other three mounting
locations.
5
Place wireguards onto the fixture so they line
up with the wireguard mounting plate holes.
(See Fig. 3)
6
Insert the bolt and attach the nut to the bottom
of the bolt to secure the wireguard in place.
(See Fig. 4 and Fig. 5)
7
Repeat Step 6 for other 7 hardware locations.
(See Fig. 6 for completed assembly)
8
Proceed to mount fixture per customer selected
mounting method and complete electrical
connections to NEC/local code.
A
2
4
5
1
3
WARNING!
Risk of fire or electric shock. To reduce risk
of electrical shock, turn off power supply
before installation or servicing.
1. Field installers are responsible for recognizing specific site
requirements and making adjustments to assure a complete,
functional installation.
2. Make all power connections using UL listed components.
3. Electrical connections must be made by a qualified electrician
and in accordance with NEC and local codes.
6