![Orbit Merret OM 402PWR Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/orbit-merret/om-402pwr/om-402pwr_manual_1648160026.webp)
26
| INSTRUCTIONS FOR USE
OM 402PWR
MIN A.O.
Assigning the display value
to the beginning of the AO
range
- range of the setting: -9999…9999
DEF
= 0
5.
SETTING
LIGHT
Display value for the beginning of the AO range > MIN A.O. = 0
Example
TYP. A.O.
0
Assigning the display
value to the beginning
of the AO range
0
MAX A.O.
MIN A.O.
TYP. A.O.
Setting the type of analog
output
TYP
. A.O.
Menu
Range
Description
0-20mA
0…20 mA
Er.4- T
4…20 mA
with error message indication and broken loop indication (<3,6 mA)
4-20 T
4…20 mA
with broken loop indication (<3,6 mA)
Er.4-20
4…20 mA
with indication of error statement (<3,6 mA)
4-20mA
4…20 mA
0-5mA
0…5 mA
0-2 V
0…2 V
0-5 V
0…5 V
0-10 V
0…10 V
+-10 V
±10 V
DEF
= 4…20 mA
Type of analog output - 0...10 V > TYP. A.O. = 0-10 V
Example
4-20mA
0-2 V
0-5mA
0-10 V
0-5 V
MIN A.O.
0-20mA
Er.4- T
4-20 T
Er.4-20
0-10 V
+-10 V
• • •
DISPLA
YED ONL
Y WITH OPTIONS
> ANALOG OUTPUT
Items for “Limits” and “Analog output”
are accessible only if incorporated in the
instrument.
!
Содержание OM 402PWR
Страница 9: ...INSTRUCTIONS FOR USE OM 402PWR 9 3 INSTRUMENT CONECTION ...
Страница 31: ...INSTRUCTIONS FOR USE OM 402PWR 31 5 SETTING LIGHT ...
Страница 45: ...INSTRUCTIONS FOR USE OM 402PWR 45 6 SETTING PROFI ...
Страница 71: ...INSTRUCTIONS FOR USE OM 402PWR 71 6 SETTING PROFI ...
Страница 82: ...82 INSTRUCTIONS FOR USE OM 402PWR NOTE ...
Страница 83: ...INSTRUCTIONS FOR USE OM 402PWR 83 NOTE NOTE ...