DATA LOG + / DATA LOG 2+ 

DIGITAL TIME SWITCH  

 

INSTRUCTIONS FOR USE  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
DATA LOG + / DATA LOG 2 + is a digital time switch designed for controlling any 
electrical installation. It includes the possibility of carrying out short-duration or 
pulsed operations (from 1 to 59 seconds), On and Off at a set time, repetitive 
cycles (from 1 minute to 99 hours, 59 minutes), automatic summer/winter time 
change, holiday (day/month) period, adjustable screen brightness and updating 
from an infrared remote control. All these features can be applied to channel C1, 
and to C2 if DATA LOG 2+ is used.  
 
Function menus can appear in several languages and they display a chronogram 
on screen that shows the programming for the current day.  
To view the chronogram, as well as the other unit configurations, it is only 
necessary to repeatedly press the 

 key (info) until the desired display is 

obtained. 
 
DATA LOG + has one independent voltage-free switched circuit that allows the 
programming of up to 70 operations.  
DATA LOG 2+ has 2 independent voltage-free switched circuits that allow the 
programming of up to 70 operations between channel 1 and/or channel 2.  
 

INSTALLATION  

WARNING: installation and mounting of electric apparatus shall be carried out by 
an authorised installer. 

ALL POWER MUST BE REMOVED BEFORE PROCEEDING WITH THE INSTALLATION,.  

The unit is internally protected from interference by a safety circuit. However, 
certain particularly strong fields can alter its operation. Interference can be avoided 
if the following installation rules are followed:  
- The unit should not be installed next to inductive loads (motors, transformers and 
contactors etc.)  
- It is recommended to provide a separate line for the supply (if necessary, 
equipped with a mains filter).  
- Inductive loads must be fitted with interference suppressors (varistor, RC filter).  
If the time switch is used in combination with other units at an installation, it is 
necessary to check that the assembly so formed does not generate parasitic 
interference.  

THE POWER SHALL ONLY BE RESTORED WHEN THE EQUIPMENT IS COMPLETELY 

INSTALLED. 

 

MOUNTING  

Electronic control device for independent installation in distribution cabinet fitted 
with symmetrical 35 mm profile in accordance with the standard EN 60715 (DIN 
Rail EN 60715 (Rail DIN). 
 

CONNECTION  

Connect the mains supply according to the following schematic:  
 
 
 
 
 
 
 
 
 
 
The Line and Neutral position must be respected, checking the connections made. 
A wrong connection can destroy the unit.  
 

PUTTING IN SERVICE 

For the device to be able to execute control over the installation, IT MUST BE 
POWERED UP. 
The display will light up and the MAIN screen will appear.   
When the equipment is switched off, the screen will also be off, but the date, time 
and all programming will be maintained during the four-year lifetime of the 
incorporated lithium battery. 
In this case, if any key is pressed, the display will temporarily switch on to allow 
programming. If no keys are pressed during fifteen seconds, the display will be 
switched off again. 

 

These units have an LCD panel and four keys for adjustment and programming. 
The following information is shown on the LCD:  

  Day of the week in text line 1 in the ON state 

  Complete time and date  

 Symbol 

 = Vacation state 

  Chronogram with the operations for that day 

  State of circuits C1 / C2: ON 

, OFF 

 

 INFO symbol   

 

PERMANENT

 text in line 2 (if activated) 

 

OFF

 text in line 1 (if in switched-off state)  

  LOG technology: two text lines for programming help menus  

  Two lines of text in programming help menu style and a chronogram with 

48 divisions in which each segment represents thirty minutes 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

CONFIGURATION 

DATA LOG +/ DATA LOG 2+ units leave the factory configured with the current 
date and time, and configured as follows:  
Hour Mode:  

24 h 

W-S Change 

Automatic (last Sunday of March) 

S-W Change 

Automatic (last Sunday of October) 

Vacations: NO 

(deactivated) 

Programs: 

None (memory empty) 

 

PROGRAMMING 

The programming is based on menus and submenus through which we can move 
to program operations or make adjustments to the unit. Access to the main menu 
from the idle screen is by pressing key 

. Use the 

 and 

 keys to step through 

the different menus, which can be entered by pressing key 

. To go back to the 

previous menu, press key 

C

 
The data to be entered always appear flashing on the screen. 
The structure of the menus is the following:  
 

MAIN MENU  

 

PROGRAMS. 

This is the menu where the different operations are programmed. 

There are 70 memory slots (from PROG_01 to PROG_70). 

 

o

 

ENTER. 

Where we will edit the different programs. With the 

 and 

 keys, 

we can step from PROG_01 to PROG_70. After selecting one, it is entered 
by pressing 

. Once inside the program, we have the following options:  

-

  EDIT. The message “PROG_01: EDIT” is shown on screen. By 

validating with 

 TYPE C1: ON appears on screen. The type of 

operation for the DATA LOG is selected with the 

 and 

 keys: C1: 

ON, C1: OFF, C1: PULSE, C1: CYCLE. In the case of DATA LOG 2+, 
we also have C2: ON, C2: OFF, C2: PULSE, C2: CYCLE. The choice 
made is validated with key 

. Next the hour, minute and combination of 

days of the week are chosen for the operation.  
In the case of PULSES, it will be necessary to specify the pulse 
duration in seconds.  
In the case of CYCLES, it is necessary to specify when the cycle will 
begin (hour, minute and day of the week); and then, when the cycle 
finishes (hour, minute and day of the week). To end the CYCLE 
definition, it would only remain to indicate the ON period and the OFF 
period respectively (in hours and minutes). 

-

  COPY. It copies the operation of a program for use in another.  

-

  PASTE. It pastes the previously copied operation.  

-

  ERASE. It deletes the selected program.  

o

 

ERASE. 

It allows a deletion to be carried out of all the operations in the 

programs in one step. 

 

 

 

CLOCK. 

This will set the equipment time. The variables to be configured are (in 

this order): year, month, day, hour and minute. The day of the week is 
automatically calculated.  

 

 

 

PERMANENT. 

This is the menu in which we can fix a permanent operation (On 

/ Off) of channel C1, and of channel C2 in the case of DATA LOG 2+. With the 

 and 

 keys we step through the different options: 

C1: YES 

Æ

 

C1: NO 

Æ

 

C2: 

YES 

Æ

 

C2: NO. 

We validate the case we want with 

. The equipment will not 

follow the operations programming for the selected channel if OPTION YES is 
selected. 
The contact position can be changed manually.

 

 

 

LANGUAGE. 

This is the menu where the unit language is set. 

 

 

 

SETTINGS. 

This is the menu in which most of the unit configurations can be 

carried out. 

 

o

 

SEASON. 

It establishes the time change mode 

Summer - Winter

 and 

Winter 

- Summer

.  

-

  AUTO. It automatically carries out the time change on the last Sunday of 

March and on the last Sunday of October.  

-

  MANUAL. It allows the day and time to be chosen for carrying out the time 

change.  

-

  DESACT. The time change is not carried out.  

DAY OF THE WEEK

CHRONOGRAM

INFO SYMBOL

DATE

CURRENT TIME

HOLIDAY
SYMBOL

INFO SYMBOL

CIRCUIT 2
STATUS

STANDBY STATUS DISPLAY

C1 (INFO) STATUS DISPLAY

CIRCUIT 1
STATUS

3

2

1

6

5

4

N

L

M

~

ON

C1

  1 - 2

C2

  4 - 5

C1

C2

3

2

1

N

L

M

~

C1

DATA LOG +

DATA LOG 2+

OPEN

CLOSE