Sun Datacenter InfiniBand Switch 648 Installation Guide • May 2010
■
(Optional) Display and record the power supply FRU ID information.
See
“Identify the Power Supply Addresses” on page 90
■
Power on the fabric cards.
See
“Enable the Fabric Cards for Installation” on page 93
Related Information
■
Switch Command Reference
,
psustatus
command
■
“Verify the CMC Status” on page 86
■
“Verify the Fabric Card Status” on page 97
■
“Verify the Line Card Status” on page 104
■
“Check Link Status” on page 116
▼
Identify the Power Supply Addresses
1. Identify the prerequisite and subsequent tasks you must perform in
conjunction with this procedure, to install the switch.
See the table in
“Installation Sequence” on page 20
.
2. Use this table to provide the IPMB address or FRU number for a power supply
in a particular slot.
3. Display and record the power supply FRU ID information.
See
“Display the Power Supply FRU ID Information” on page 91
Related Information
■
Switch Administration
, component addressing
■
“Identify the CMC Addresses” on page 87
■
“Identify the Fabric Card Addresses” on page 99
■
“Identify the Line Card Addresses” on page 106
■
“Identify the CXP Connector Addresses” on page 117
Slot Number
IPMB Address
(in hexadecimal)
FRU Number
0
20
3
1
20
4
2
20
5
3
20
6
Содержание Sun Datacenter InfiniBand Switch 648
Страница 1: ...Sun Datacenter InfiniBand Switch 648 Installation Guide Part No 820 7738 12 May 2010 Revision A ...
Страница 8: ...viii Sun Datacenter InfiniBand Switch 648 Installation Guide May 2010 ...
Страница 134: ...124 Sun Datacenter InfiniBand Switch 648 Installation Guide May 2010 ...
Страница 140: ...130 Sun Datacenter InfiniBand Switch 648 Installation Guide May 2010 ...