Determine Which Power Supply Is Faulty
Determine Which Power Supply Is Faulty
Check if the following LEDs are lit when a power supply fault is detected.
■
Service Required LEDs on the front and rear panels.
■
Rear PS Fault LED on the front panel.
■
Service Required LED on the faulted power supply.
Related Information
■
“Power Supply LEDs” on page 83
■
“Front Panel Components (Service)” on page 13
■
“Rear Panel Components (Service)” on page 15
■
“Remove a Power Supply” on page 85
Remove a Power Supply
This is a hot-service procedure that can be performed by a customer while the server is running.
Caution -
Hazardous voltages are present. To reduce the risk of electric shock and danger to
personal health, follow the instructions.
Caution -
If a power supply fails and you do not have a replacement available, to ensure proper
airflow, leave the failed power supply installed in the server until you replace it with a new
power supply.
1.
Prepare for servicing.
“Preparing for Service” on page 45
.
If necessary, release the CMA to access the power supplies. Do not allow the CMA to hang
unsupported while it is unattached.
2.
Disconnect the power cord from the power supply that displays an amber lit
Service Action Required LED.
3.
Press down on the release latch to open the ejector arm.
4.
Slide the power supply out of the chassis.
Servicing Power Supplies
85
Содержание SPARC T8-2
Страница 1: ...SPARC T8 2 Server Service Manual Part No E80511 04 June 2019 ...
Страница 2: ......
Страница 10: ...10 SPARC T8 2 Server Service Manual June 2019 ...
Страница 12: ...12 SPARC T8 2 Server Service Manual June 2019 ...
Страница 24: ...Server Block Diagram 24 SPARC T8 2 Server Service Manual June 2019 ...
Страница 26: ...26 SPARC T8 2 Server Service Manual June 2019 ...
Страница 62: ...62 SPARC T8 2 Server Service Manual June 2019 ...
Страница 82: ...82 SPARC T8 2 Server Service Manual June 2019 ...
Страница 110: ...110 SPARC T8 2 Server Service Manual June 2019 ...
Страница 114: ...114 SPARC T8 2 Server Service Manual June 2019 ...
Страница 128: ...128 SPARC T8 2 Server Service Manual June 2019 ...
Страница 135: ...Verify the SPM Related Information Oracle ILOM documentation Install the SPM on page 131 Servicing the SPM 135 ...
Страница 136: ...136 SPARC T8 2 Server Service Manual June 2019 ...
Страница 146: ...146 SPARC T8 2 Server Service Manual June 2019 ...
Страница 164: ...164 SPARC T8 2 Server Service Manual June 2019 ...
Страница 170: ...170 SPARC T8 2 Server Service Manual June 2019 ...
Страница 176: ...176 SPARC T8 2 Server Service Manual June 2019 ...
Страница 182: ...182 SPARC T8 2 Server Service Manual June 2019 ...
Страница 188: ...188 SPARC T8 2 Server Service Manual June 2019 ...