For a usage of the CSmicro LT for online maintenance applications (in electrical cabinets e.g.) the following
recommend settings are already included in the factory default setting (but not active):
OUT
At
3-state output
the following settings are default:
Pre-alarm
difference:
2
°C
No
alarm
level:
8
V
Pre-alarm
level:
5
V
Alarm level:
0 V
Service
voltage:
10
V
IN/
OUT: At
Alarm output (open collector)
the following settings are default:
Mode:
normally
closed
Temp code output:
activated (for values above alarm level)
Range settings:
0 °C = 0 %/ 100 °C = 100 %
Vcc
adjust:
If
activated
the following settings are default:
Output
voltage
range:
0-10
V
Difference
mode:
activated
Alarm level
Alarm value (IN/ OUT pin)
Vcc
1
40 °C
11 V
2
45 °C
12 V
3
50 °C
13 V
4
55 °C
14 V
5
60 °C
15 V
6
65 °C
16 V
7
70 °C
17 V
8
75 °C
18 V
9
80 °C
19 V
10
85 °C
20 V
optris CSmicro – E2011-08-B
6