CHAPTER 2: USAGE NOTES AND SPECIFICATIONS
SNAP High-Density Digital Module User’s Guide
19
Output Modules
SNAP-ODC-32-SRC
SNAP-ODC-32-SRC-FM
SNAP-ODC-32-SNK
SNAP-ODC-32-SNK-FM
Switching Voltage
5–60 VDC
5–60 VDC
Nominal Switching Voltage
12–24 VDC
12–24 VDC
Logic Voltage and Current
5 VDC ± 0.1 @ 150 mA
5 VDC ± 0.1 @ 150 mA
Maximum Off State Voltage
60 VDC
60 VDC
Output Leakage, Typical
<10 microamps per channel (60 V, 70
°C)
<10 microamps per channel (60 V, 70 °C)
Maximum Load per Point
0.25 A
0.25 A
Voltage Drop
0.15 VDC @ 0.25 A
0.15 VDC @ 0.25 A
Surge (1 sec.)
1 A
1 A
Output Arrangement
32 output channels; 4 groups of 8 out-
puts each. Points in each group share a
common positive connection.
32 output channels; 4 groups of 8 outputs
each. Points in each group share a common
negative connection.
Maximum Operating
Common Mode Voltage
250 V
250 V
Isolation: Field to Logic
1500 V
1500 V
Output Turn-On/Off Time
100 microseconds
100 microseconds
Polling time from I/O processor
to module
1
2–30 ms typical
2
2–30 ms typical
2
Indicators
None; use optional OptoTerminal-G20
diagnostic display or breakout rack.
None; use optional OptoTerminal-G20 diag-
nostic display or breakout rack.
Maximum Number of HDD
Modules on One Mounting
Rack
16
16
Torque, hold-down screws
4 in-lb (0.45 N-m)
4 in-lb (0.45 N-m)
Torque, connector screws
5.26 in-lb (0.6 N-m)
5.26 in-lb (0.6 N-m)
Operating Temperature
-20 to 70 °C
-20 to 70 °C
Storage Temperature
-40 to 85 °C
-40 to 85 °C
Agency Approvals
SNAP-ODC-32-SRC: UL, CE, RoHS,
DFARS
SNAP-ODC-32-SRC-FM: CE, FM,
RoHS, DFARS
SNAP-ODC-32-SNK: UL, CE, RoHS,
DFARS
SNAP-ODC-32-SNK-FM: CE, FM, RoHS,
DFARS
Warranty
Lifetime
Lifetime
1 Affects turn-on and turn-off determination
2 Time varies based on the SNAP PAC I/O processor (brain or on-the-rack controller), processor configuration, and
Ethernet host communication activity.