22

23

"Err 3" is indicated when the Analog Signal Input (4 to 20mA) from 
the Detector is out of input range (lower than 3.5mA or upper than 
22mA).

"Err 5" is indicated when 20mA Analog Signal Input at the time of 
the Span-Adjustment is not within 

±

2mA.

"Err 4" is indicated when 4mA Analog Signal Input at the time of the 
0-Adjustment is not within 

±

0.5mA.

"Err 6" is indicated when the setting range is exceeded.

"Err 2" is indicated when calibration is not carried out properly.

"Err 1" is indicated when the Detector is out of order, and so forth. 

8

The SC-T4 has an Error Indication function to indicate improper 
operation and occurrence of problem. There are six kinds of error 
indications (Err 1 to Err 6), the meaning of which is as follows.

Error Indication

"Err 1" is indicated 
on the Display, 
and an alarm 
indicator is lit up.

"Err 2" is 
indicated on the 
Display.

The Detector is out of 
order, and so forth.

A Detector Cable is not 
wired properly.

Check this according to the "Troubleshooting" 
in an instruction manual for the Detector.

After checking the Detector Cable for 
wiring, wire it properly.

"Err 3" is 
indicated on the 
Display.

"Err 4" is 
indicated on the 
Display.

The Detector needs repair. Contact your 
dealer.

Carry out calibration once again. If "Err 2" 
persists in indicating even when carrying 
out calibration repeatedly, it is necessary 
to make repairs. Contact your dealer.

The Display is 
not turned on.

"Err 6" is indicated 
on the Display.

"Err 5" is 
indicated on the 
Display.

The Detector is out of 
order.

A Detector Cable is not 
wired properly.

The Detector is out of 
order.

A Detector Cable is not 
wired properly.

The Detector is out of 
order.

The Detector Windows 
are soiled.

A Detector Cable is not 
wired properly.

The setting is not made 
properly.

The Transmitter is out of 
order.

A Power Cable is not 
wired.

A Circuit Breaker is at 
the "Breaker On"position.

A Detector Cable is not 
wired properly.

The Detector is out of 
order.

The Detector Windows are not 
light-shielded completely.

Calibration turns out a 
failure.

After checking the Detector Cable for 
wiring, wire it properly.

The Detector needs repair. Contact your 
dealer.

After checking the Detector Cable for 
wiring, wire it properly.

The Detector needs repair. Contact your 
dealer.

After checking the detector cable for 
wiring, wire it properly.

The Transmitter needs repair. Contact 
your dealer.

After checking the internal wiring, wire 
the Power Cable properly.

Get rid of possible cause of the circuit breaker being at the 
projected position before depressing the Circuit Breaker.

The setting is out of range. Each setting should be 
made within the range that Err 6 is not indicated.

After checking the Detector Cable for 
wiring, wire it properly.

The Detector needs repair. Contact your 
dealer.

Completely light-shield the Detector 
Windows and make adjustments again.

By referring to an instruction manual of the Detector, 
clean the Windows and make adjustments again.

Problem

Cause

Inspection and corrective action

Normal Position

"Breaker On" Position

9

Troubleshooting

Содержание SS Checker SC-T4

Страница 1: ...is instruction manual should be kept for future reference such as maintenance Transmitter Instruction Manual 2007 7 59 1362 1 For more information on OPTEX products contact your dealer or visit our we...

Страница 2: ...ture reference such as maintenance Transmitter Instruction Manual 0 1 Table of Contents 1 For safe use 2 External Features 3 Installation Installation Wiring Extension of Detecter Cable 4 Operation Pa...

Страница 3: ...ve gas is in danger of intruding through the piping etc into the Transmitter Do not bind the signal output cable with the power cable or do not put them in the one Cable Clamp Install the transmitter...

Страница 4: ...t On Transmitter Operation panel Display 2 External Features Cover Cable Clamps Key Hook Lock Lever Power Switch Circuit Breakers Terminal Block Operation Buttons Display Terminal Cover Alarm Level In...

Страница 5: ...luding wiring resistance For connection to the Self Checking Relay Output terminal and Alarm Relay Output terminal load resistance should be 240 VAC and 1A Max Although a protective circuit is built i...

Страница 6: ...o carry out Fine Adjustment of Signal Output Low Limit 4mA Press the upper and lower arrow buttons simultaneously to carry out Fine Adjustment of Signal Output High Limit 20mA Move the digit to be ent...

Страница 7: ...d water or ion exchange water 1 Clean the Detector and the Detector Windows Every time the MODE button is pressed the Display is changed into each setting To change the setting value select the item a...

Страница 8: ...s not 1000 use to change the Display into 1000 indication When the display shows 1000 press to terminate the 0 Span Adjustments 8 Press for 2 seconds or more SPAN blinks on the Display Pip Pip Pip 4 A...

Страница 9: ...ayed the value is out of the setting range Alarm Timer can be set for 1 to 120 minutes or OFF Setting unit is 1 minute The Alarm Timer is set for OFF as a factory setting Alarm Timer Setting Ex To set...

Страница 10: ...d lower arrow buttons button increases a numeric value and button decreases the value While pressing buttons the values displayed are continuously changed To cancel the Signal Output Low Limit Setting...

Страница 11: ...Pip Pip Fine Adjustment of Signal Output 6 Fine Adjustment of Lower Limit 4mA and Upper Limit 20mA of Signal Output 4 20mA can be made When both right and left arrow buttons are pressed simultaneously...

Страница 12: ...es measured by the official method and the values indicated by SC T4 at a place where the instrument is installed Indicated values Indicated values 1 2 The following calculating formula is used Span s...

Страница 13: ...indicated on the Display Err 5 is indicated on the Display The Detector is out of order A Detector Cable is not wired properly The Detector is out of order A Detector Cable is not wired properly The D...

Страница 14: ...Power Supply for Sensor 12 VDC Signal Output analog 4 20mA resistance load of 300 or less Self checking Relay Output non voltage C contact capacity 240 VAC 1A resistance load Alarm Relay Output non vo...

Отзывы: