-5-
12 m (40 ft.)
3.0
m
(10
ft.)
If the base of the unit is already parallel to the ground,
• Do not change the detection distance by tilting the unit up or down.
•
Always use the Masking seals.
•
Walk test the unit to ensure that the disired detection distance is achieved.
Tighten the adjustment screw.
Wire to the terminal and install the
Main unit and lens on the base.
On the Main unit, make the settings
and check operation.
Using 6-B as reference, adjust the up-
down orientation, then tighten the lock
screw.
Fit the shaft cover into place.
Caution>>
8
5
6
7
Once the operation checks are
complete, fit the shaft cover into place.
When the Main unit is fastened to the
bracket, you can not remove the shaft
cover.
Caution>>
9
6-B
Detection distance check and up-down angle adjustment
Adjustment
screw
The LED lights when you
come closer within
9 m (30 ft.).
Adjust the angle upward.
Carry out the walk test again.
The LED lights at
12 m (40 ft.).
There is no need to adjust
the up-down angle.
The LED lights at a
point farther than
13 - 14 m (43 - 47 ft.).
Adjust the angle downward.
Carry out the walk test again.
In cases where he ground is not parallel with the base of the unit the correct detection
distance will not be obtained. In such cases, a walk test will be required. To ensure that the
required area of detection is achieved.
Complete walk test from outside the walking area
to inside. Check that at a distance of 12 to 13m
(40 to 43ft.)
from the Main unit, the sensor detects
the person and the LED lights.