Warning  Indication (OA-603 Sensor head)

TROUBLE SHOOTING

Advise the building owner/operator of the following items

1.  When turning the power on, stay clear of detection area for a minimum of 10 seconds then walk test detection 

       area to ensure proper operation. 

2.   Always keep the detection window clean. If dirty, wipe the window with a damp cloth ( Do not use any cleaner or solvent ).

3.   Do not wash the sensor with water. 

4.   Do not disassemble, rebuild or repair the sensor yourself; otherwise electric shock may occur. 

5.  Contact your installer or the sales engineer if you want to change the settings.

6.  Do not place an object that moves or emits light in the detection area.(ex. Plant,  illumination etc..)

7.   Do not paint the Detection Window. 

“Take Care of Environment”.  This manual uses recycled paper.

OPTEX CO.,LTD. 

(ISO 9001 Certified by LRQA)

5-8-12 ogoto Otsu,

520-0101 Japan

TEL.: +81 (0)77-579-8700  

FAX : +81 (0)77-579-7030

WEBSITE: www.optex.co.jp

Secumatic b.v.

Tiber 2 . 2491 DH The Hague , P.O. Box 24009

2490 AA The Hague The Netherlands

TEL.: +31 (0)70 419 41 00 

FAX : +31 (0)70 317 73 21

E-MAIL: [email protected]

WEBSITE:  www.secumatic.nl

Optex Technologies, Inc.

3882 Del Amo Blvd., Suite 604,

Torrance, CA 90503-2184, USA

TEL: 

+1 (310) 214-8644

FAX: 

+1 (310) 214-8655

TOLL-FREE: +1 (800) 877-6656

WEBSITE: www.optexentrances.com

Contact your installer or the sales engineer if:

 - you need to change the settings or replace the sensor.
 - the trouble still persists after checking and remedying as described above.

1-8

Symptom

Possible cause

Solution

OC-904C no LED indication

OC-904C LED double orange flashing & no LED 

indication on OA-603

CANNOT INITIATE SETUP

WILL NOT COMPLETE INITIAL SETUP

Improper power supply

Correct power problem

Bad connection on Orange and Brown wires of OC-904

Repair bad connection

Bad connection at OC-904

Reseat 4 pin connector from Loop assy to OC-904

Bad connection from loop assy 

To OA-603 sensor head

Reseat 4 pin connector from loop assy to OA- 603 sensor head

Bad connection with 7" pass thru cable

Reseat connection of 7" cable to both OA-603 sensor heads

Bad 7" cable

Replace as necessary

OC-904 LED double orange flashing & erratic LED 

on OA-603 sensors

Switches 7 & 8 of left dipswitches on OA-603 sensors set wrong

Correct dipswitch settings see pg 1-2

OC-904 dipswitches set wrong

Check Connection Matrix for proper dipswitch settings

Poor or improper connection of yellow wires from OC-904 to door control Check Connection Matrix for proper  connection of yellow wires

Improper voltage on red & black wire of OC-904

Ensure positive voltage on red wire at hold open and 0 voltage 

at closed position

INTERMITENT RECYCLE (ghosting) OR INTERMITENT STALLING

After initial setup door ghosts several times on first activation

Happens on 15% of installations 

If stops after first activation, system is OK

OA-603 sensor head not mounted flush on door

Head may be resting on top of loop mounting bracket 

Reposition head flush on panel

Improper threshold or swing area angle adjustment

Set threshold and swing area angles at +5 degrees (deep)

Improper voltage on red & black wire of OC-904

Ensure positive voltage on red wire at hold open and 0 voltage 

at closed position

Stalling caused by traffic just outside of swing path or objects 

near guide rails

Set switch 6 on left bank dipswitch of OA-603 on/up (shallow) 

Note: moving the dipswitch will initiate a setup

Area width dipswitches set wrong  

(right bank dipswitches on OA-603)

Verify proper settings (page 1-2)

Inconsistent data from position sensor/loop assy

Postion the loop assy so loop center coupler does not rest on 

door at any point of door travel 

NO ACTIVATION AND/OR NO REACTIVATION ON CLOSING CYCLE

OC-904 yellow wires poor or improper connection to door control

or on/off/hold switch

Verify proper connection and output of yellow wires. 

(see Elite Connection Matrix)

OC-904 dipswitches set improperly

Verify proper settings(see Elite Connection Matrix)

On knowing act applications poor or improper connection of 

purple wires from OC-904 to activation device

Verify good and proper connection (see OC-904 install manual)

NO SAFETY ON SWING SIDE AT FULL 

CLOSED

OA -603 sensor detects (solid or flashing red LED) 

but door opens anyway

Poor or improper connection of Blue wires from OC-904 to door 

control

Verify good and proper connection of blue wires 

(see Elite Connection matrix)

OC-904 dipswitches set improperly

Verify proper settings (see Elite Connection Matrix)

OA-603 no detection (solid green LED)

Area width dipswitches set wrong

(right bank dipswitches on OA-603)

Verify proper settings (page 1-2)

NO STALL ON SWING SIDE WHILE 

DOOR IS OPENING

OA -603 sensor detects (solid or flashing red LED)

but door does not slow or stop

Poor or improper connection of green wires from OC-904 to door

control

Verify good and proper connection of Green wires 

(see Elite Connection matrix)

OC-904 dipswitches set improperly

Verify proper settings (see Elite Connection Matrix)

OA-603 no detection (solid green LED)

Area width dipswitches set wrong 

(right bank dipswitches on OA-603)

Verify proper settings (page 1-2)

DOOR REMAINS OPEN

OC-904 dipswitches set improperly

Verify proper settings (see Elite Connection Matrix)

On knowing act applications poor or improper connection of 

purple wires from OC-904 to activation device

Verify good and proper connection (see OC-904 install manual)

Improper wiring of door equipment on/off/hold switch

Verify proper wiring of on/off/hold switch

Moving dipswitch on OA-603 does not 

result in OA-603 LED fast flash yellow.

Mode

Self Monitoring Function

Life cycle Notification

Signal Saturation

Communication Error

Setting Error

Operation Indicator

Explanation

Fast Green Blinking

Twice Green Blinking

Slow Green Blinking

The sensor is reaching the 
end of its life cycle.

The relay is reaching the
end of its life cycle.

Either the mounting position is too 
low or the detection area includes 
the wall or another object. 
OA-603 threshold angle may be
set to less than +5 degrees deep.
Refer to "ADJUSTMENT".

The sensor cable is connected,
but unstable communication. 
A sensor cable may be 
disconnected or OA-603 mode
switches 7 & 8 may be set wrong.
Refer to "ADJUSTMENT"

When all the area width switches
are inactive.
Refer to "ADJUSTMENT".

Fast Orange Blinking

Twice Orange Blinking

Содержание Elite OA-603

Страница 1: ...6 7 8 9 9 10 MANUFACTURER S STATEMENT For ease of installation and proper operation read thru this manual especially WARNING CAUTION NOTE prior to installing and adjusting the sensor system Failure t...

Страница 2: ...wing CLOCKWISE to achieve maximum angle for all door mount sensor The screws will continue to turn even though maximum angle is reached as indicated by the angle gauges Please refer to the following f...

Страница 3: ...ch the sensor head loosely to the door leaf with two of the nine supplied screws 3 Align the position sensor mounting plate with the appropriate mounting holes and securely fasten to the door leaf wit...

Страница 4: ...he loop does not touch the door panel throughout the door travel 2 Once the ideal position is determined turn the screw in the back of the cover clockwise to secure the cover in place 1 Remove knockou...

Страница 5: ...g Midpoint Two different frequencies can be set by adjusting Dipswitches 3 When two or more sensors are mounted close to each other they may interfere When that happens change Frequency Setting the Au...

Страница 6: ...omplete in less than 5 seconds initiate setup again Door Status Sensor Status Operation Indicator Swing Side Approach Side Initial Setup door closed Yellow Blinking Solid Yellow Yellow Blinking Aproxi...

Страница 7: ...CHECKING Operation Check Before leaving the site check ve items in the right table 1 7...

Страница 8: ...s deep Improper voltage on red black wire of OC 904 Ensure positive voltage on red wire at hold open and 0 voltage at closed position Stalling caused by traffic just outside of swing path or objects n...

Страница 9: ...TACT ACTIVATION OPERATION N O N C STALL RELAY CONTACT FUTURE DEVELOPMENT N O N C AUTO KNOWING ACT NOTE For Knowing Act application Connect purple wire to Activate output from push button The approach...

Страница 10: ...not mounted flush on door Head may be resting on top of loop mounting bracket Reposition head flush on panel Improper threshold or swing area angle adjustment Set threshold and swing area angles at 5...