background image

Control unit STG 1.2

2

 | 

8

  |  Fire Protection  |  Data sheet No. 43104  | Version 02-2016

Operation

 The STG is intuitively operated by means of 4 keys:

The STG 1.2 has two menu levels available:

• 

Home menu:

• 

Display overall status / overview

• 

Submenus:

• 

Save and delete the configuration  
(switch to operating mode or service mode)

• 

Address assignment for the STG  
(if multiple STGs are to be integrated in one bus)

• 

Bus scan of the connected detectors

• 

Detailed view of the connected duct smoke detectors 
(detector status, detector contamination level)

• 

Display of the STG firmware

By pressing the Home button the Home menu is always called 
up. The Home menu is reached by pressing the up or down 
button in the various sub-menus. The exact functionality is 
described in plain text in the relevant sub-menu on the display.

2 operating states for the STG must be differentiated:

• 

Service mode:

 

In service mode, the failure LED flashes and the text “Service 
Modus” blinks in the display. The “Service” relay drops out 
(terminal 21 + 23 open, terminal 21 + 22 closed). 
 
As long as no configuration is saved, the STG is always in ser-
vice mode and it will continuously carry out a bus scan.  
 

By simultaneously pressing the up and down keys an existing 
configuration will be stored in the submenu. When the config-
uration is stored it will automatically leave the service mode. 
 

Note:

 The service mode is used to integrate a new detector or 

for system maintenance. 

• 

Operating mode: 

The operating mode is accessed by storing the selected 
configuration. All connected detectors will be monitored and 
failures/alarms will be evaluated. The operating mode can be 
left by deleting the stored configuration. 
 
All connected smoke alarms can be displayed in the sub-
menu with the up and down keys. This is where the detector‘s 
bus address, status, and contamination (only with ceiling 
smoke detectors) are displayed. 
 
Alarms and error messages are self-sustaining and must be 
acknowledged once more on the STG (with the alarm / reset 
button) after correction.

Functionality test

By pressing the reset button for a few seconds all the LEDs light 
up and all the relay inputs are connected.

Installation instructions

All work must be carried out by a sufficiently qualified crafts-
man. Current local rules and regulations (e.g. building regula-
tions, electrical/VDE guidelines, etc.) are to be observed. 
Installers and operators are required to be adequately infor-
med before operation. We assume no liability for misprints 
and changes after printing. Compliance with operating and 
installation instructions is also included within the regulations 
of intended use. We assume no liability for damages caused 
by improper use. Operating licenses and guarantees and all 
warranty claims will be voided in the event of unauthorized 
modifications or any tampering with the device.

Alarm
Contamination
Operation
Failure

Содержание STG 1.2

Страница 1: ...em ring buses Smoke alarms failure and contamination messages are all forwarded from the detectors to the STG and shown on a display This makes it possible for a technician or custodian to supervise a...

Страница 2: ...ervice mode Note The service mode is used to integrate a new detector or for system maintenance Operating mode The operating mode is accessed by storing the selected configuration All connected detect...

Страница 3: ...rding to electrotechnical regulations Please ensure to connect the current ceiling smoke detector model The older version type DRM 3 3 has been replaced by version DRM 3 3 N Contact depictions are wit...

Страница 4: ...ld be installed in a separate conductive and grounded cable trunking It is important to ensure that no potential differences between devices can occur on the Modbus perform equipoten tial bonding The...

Страница 5: ...reafter the data register follows The register set is dependent on the query and can vary between 1 and 125 Register description Each register consists of 2 bytes With Modbus RTU it is possible to sen...

Страница 6: ...lure LED lights up 0 Failure LED does not light up Bit 12 1 Operation LED lights up 0 Operation LED does not light up Bit 11 1 Alarm relay energized 0 Alarm relay de energized Bit 10 1 Failure relay e...

Страница 7: ...ctor has an internal error 0 No internal error Bit 3 1 Malfunction Detector no longer recognized in the bus 0 No malfunction Bit 2 1 Alarm 0 No alarm Bit 1 0 0 No detector connected at this address 1...

Страница 8: ...yte 3 Byte 4 Byte 5 STG address Function Error code CRC LSB CRC MSB Byte 0 Address of the STG 1 2 Byte 1 Function byte Here the function byte for the query is sent back However the MSB is set by the f...

Отзывы: