Fire Protection  |  Data sheet No. 43104  | Version 02-2016  | 

3

 | 

8

Control unit STG 1.2

Electrical connection

Work on electrical systems or equipment must be carried out only by a qualified electrician or by instructed personnel under the 
direction and supervision of a qualified electrician according to electrotechnical regulations.

Please ensure to connect the current ceiling smoke detector model. The older version, type DRM 3.3, has been replaced by version 
DRM 3.3-N.

Contact depictions are with the 
power off (alarm)

Contact depictions are with the 
power off (alarm)

Connection of type DRM 3.3

Connection of type DRM 3.3-N

The power supply to the detector takes place via the system ring bus. The current in the ring bus is limited to 1 A.  
The bus line is to be shielded on both sides.

Содержание STG 1.2

Страница 1: ...em ring buses Smoke alarms failure and contamination messages are all forwarded from the detectors to the STG and shown on a display This makes it possible for a technician or custodian to supervise a...

Страница 2: ...ervice mode Note The service mode is used to integrate a new detector or for system maintenance Operating mode The operating mode is accessed by storing the selected configuration All connected detect...

Страница 3: ...rding to electrotechnical regulations Please ensure to connect the current ceiling smoke detector model The older version type DRM 3 3 has been replaced by version DRM 3 3 N Contact depictions are wit...

Страница 4: ...ld be installed in a separate conductive and grounded cable trunking It is important to ensure that no potential differences between devices can occur on the Modbus perform equipoten tial bonding The...

Страница 5: ...reafter the data register follows The register set is dependent on the query and can vary between 1 and 125 Register description Each register consists of 2 bytes With Modbus RTU it is possible to sen...

Страница 6: ...lure LED lights up 0 Failure LED does not light up Bit 12 1 Operation LED lights up 0 Operation LED does not light up Bit 11 1 Alarm relay energized 0 Alarm relay de energized Bit 10 1 Failure relay e...

Страница 7: ...ctor has an internal error 0 No internal error Bit 3 1 Malfunction Detector no longer recognized in the bus 0 No malfunction Bit 2 1 Alarm 0 No alarm Bit 1 0 0 No detector connected at this address 1...

Страница 8: ...yte 3 Byte 4 Byte 5 STG address Function Error code CRC LSB CRC MSB Byte 0 Address of the STG 1 2 Byte 1 Function byte Here the function byte for the query is sent back However the MSB is set by the f...

Отзывы: