| Fire Protection | Data sheet No. 40105 | Version 08-2020
Mounting and electrical connection
All work (such as installation, electrical connection, startup,
operation, and maintenance) must only be performed by
sufficiently qualified tradesmen. The respectively applicable
local rules and regulations (e.g. national building codes,
electrical/VDE regulations, etc.) must be observed. Installers
and operating entities are required to sufficiently familiarize
themselves before startup. Read the product description before
operating the equipment. Verify that the product can be used
for the relevant application without restrictions. We are not
liable for printing errors and changes after printing. Appropriate
use implies compliance with operating and installation
instructions. We are not liable for losses due to inappropriate
use. Unauthorized or inappropriate manipulations or
modifications of the device render the operating permit,
the product warranty and warranty claims null and void.
Use dowels and screws to mount the socket on the ceiling
and route the cable through the center opening. The detector
locks onto the socket with a bayonet joint. Remove the plastic
tab from the bottom of the smoke detector before locking the
detector onto the socket. A tool with a diameter of ca. 3 mm
is required to dismount the detector.
Wiring diagram for operation with control unit ABAV-S3
Wiring the socket
1
2
5
6
3
4
1
2
5
6
3
4
1
2
5
6
3
4
14 13 12 11
10 9
8
ABAV S3
Control unit
Terminal
resistor
2.2 kOhm
Max. 30 detectors in total!
Optional
external LED indicator
(12 VDC, 20 mA)
Plastic tab on smoke detector
Unlocking the detector