COMMUNICATION AND INTERFACES
24 / 42
Z800-3000_usermanual_engl_updated_202001.docx
5.2 Slot for interface cards
The ZINTO features a slot (see Chapter 8.2
) for the follow-
ing interface cards:
Product no.
Description
DW7SNMP30
SNMP adapter Basic
The SNMP adapter communicates via TCIP/IP with the load at-
tached to the network.
DW5SNMP30
SNMP adapter Professional
Works like
Basic
, but with additional interface for temperature sen-
sor and building management.
DWAS400DC
AS400 relay card
Combined slot card for optional communication with IBM AS400
servers or individual use of relay contacts. The following mes-
sages/contact outputs are available: UPS normal mode, standby
mode, battery mode, battery voltage low, bypass mode (XANTO
only), aggregated error, input for UPS shutdown.
Table 8: Interface cards
PLEASE NOTE
The interface cards installed in the slot can be used in parallel
with the RS-232 or USB communication.
5.3 Emergency Power Off (EPO) function
The Emergency Power Off (EPO) function is used to remotely shut
down the UPS system and connected load immediately. This means
removing the bridge on the emergency power off connector (back of
UPS system, see Chapter 8.2
) and connecting an external
emergency power off switch.
Cross section of connecting cable = 0.5 - 2.5mm
2
(AWG 13 - 20)
Recommended cross-section of connecting cable = 1.5mm
2
(AWG 15)