T R O U B L E S H O O T I N G
135 / 222
XS700-XS3000_manual_ger_eng_it_V1.1.2.doc
...........................................................
R. Kistler
Alarm signal or
status
Possible causes
Measure
Batteries
disconnected
LED on
Audio signal eve-
ry second
The UPS system does not
detect the inner batteries.
Check whether all batteries are
properly connected.
Please contact support.
Overload
LED on
Audio signal eve-
ry second
The energy requirement ex-
ceeds the capacity of the
UPS system.
Disconnect several parts of the con-
nected systems from the UPS sys-
tem. UPS operation continues, how-
ever, the UPS system may switch in-
to bypass mode or shut down if the
increased load continues. The warn-
ing messages reset as soon as the
state becomes inactive.
Over Tempera-
ture
LED on
Audio signal eve-
ry second
The internal temperature of
the UPS system is too high
or a fan has failed.
The UPS system generates
the warning message on the
warning
message
level,
however, remains in the cur-
rent operating mode.
If the temperature increases
by an additional 10°C, the
UPS system will switch to
bypass mode or shut down
if bypass mode is not avail-
able.
If the UPS system switches to by-
pass mode, it will return to normal
mode once the temperature has fall-
en 5°C below the warning message
threshold
If the state continues, the UPS sys-
tem shuts down. Ensure that the
ventilation openings are free and
remove any sources of heat. Allow
the UPS system to cool down.
Check whether an unhindered air-
flow is ensured around the UPS sys-
tem. Restart the UPS system.
Please contact support.
Battery overvolt-
age
LED on
Audio signal eve-
ry second
The voltage of the batteries
of the UPS system is too
high.
The UPS system switches the
charging device off until the next
charging cycle.
Please contact support.
Cable Fault
LED on
Audio signal eve-
ry second
The polarity of the input
connector of the UPS sys-
tem is incorrect.
Rotate the Schuko connector by
180°.
There is no ground connec-
tion.
Have the cable fault rectified by a
qualified electrician.
Special case IT system (Fr.
Isolé Terre): E.G. hospital,
ship and train.
Change it to "Disabled." Otherwise
does not start up UPS.
Содержание ONLINE XANTO S 1000
Страница 2: ...2 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 72: ...T E C H N I S C H E D A T E N 72 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler 9 3 CE Bestätigung ...
Страница 74: ...74 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 76: ...76 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 146: ...T E C H N I C A L D A T A 146 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler 9 3 CE conformity ...
Страница 148: ...148 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 150: ...150 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 220: ...D A T I T E C N I C I 220 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler 9 3 Dichiarazione CE ...
Страница 222: ...222 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...