- 27 -
Revision 1.0
Installation and Set-up
Use the following method to install REPO
switch;
•
Verify that the UPS is off and unplugged
•
Remove the REPO connector from the rear of the UPS
•
Connect isolated, normally closed, dry contacts (rated at
60Vdc maximum, 30Vac RMS maximum and 20mA
maximum), between pins 1 and 2 as shown below;
•
Use stranded, non-shielded wiring – size 18 – 22 AWG.
•
Replace the REPO connector into rear of UPS
•
Verify that the externally connected REPO switch is off, to
enable power to the UPS output receptacles.
•
Plug in the UPS and start the UPS by pressing the input
breaker to “ON”
•
Turn on the external REPO switch to test REPO function
•
Turn off REPO switch and restart UPS for normal operation.
Содержание OPP Series
Страница 1: ... 1 Revision 1 0 Operating Manual OPP Series On Line UPS ...
Страница 8: ... 8 Revision 1 0 General Description 1 2 General description OPP Block Diagram ...
Страница 17: ... 17 Revision 1 0 Installation and Set up 3 4 Rear Panel Features ...
Страница 48: ... 48 Revision 1 0 7 Specification 7 1 General specification ...
Страница 49: ... 49 Revision 1 0 Specification 7 1 General specification cont ...
Страница 51: ... 51 Revision 1 0 Specification 7 2 Run time chart OPP4000 OPP6000 ...