- 26 -
Revision 1.0
Installation and Set-up
3.10. REPO Configuration
The REPO connector ships as standard with a wire link to make
the connection between the pins which allows the UPS to
operate with no additional wiring for applications where REPO is
not required. For applications where REPO is required, use the
following procedure.
Operating the REPO
The REPO feature shuts down the protected equipment
immediately and does not follow the orderly shutdown procedure
initiated by any power management software.
Any devices which are operating on battery are also shut down
immediately. When the REPO switch is closed, the equipment
will not return to battery power until the UPS input is re-cycled.
This can be done by shutting down the UPS and re-starting it.