System-10 Dual Network Interface Installation Guide
Page 7
1.5 NETWORK SIGNAL CONNECTIONS
1.5.1 RS485
Use 18 – 22 twisted shielded cable for RS485, 2-wire (half-duplex) serial communications. The
cable is connected to terminal T1A. Do not exceed 4.4 in-lb (0.5 Nm) of torque when tightening the
terminals.
CAUTION
Only qualified service personnel should make connections between the System-10 BTU Meter
and the user’s external equipment. ONICON assumes no responsibility for damage caused to the
external equipment as a result of an improper installation.
!
Terminal
T1A
G terminal only used for
3-wire installations. Do
not connect shields to
this terminal.
CAUTION
Incoming and outgoing RS485 cable shield wires should be connected together, but must not be
connected to the BTU meter.
!