System-10 Dual Network Interface Installation Guide
Page 15
1.7.2 Changing the IP Address, Subnet mask and Gateway Address
Changing the IP address requires a PC with an Ethernet card and an available port. The network
interface is accessed using a web browser such as Internet Explorer. Both the PC and the BTU meter
must be configured to operate on the same IP network. Assuming the BTU meter is programmed with
the default address of 192.168.1.24, configure the PC to operate with an IP address of 192.168.1.1 and a
subnet mask of 255.255.255.0. Follow the procedure outlined below to edit the IP address, subnet mask
and gateway address.
1. Connect an RJ45 Ethernet cable between the PC and the System-10 and power the BTU meter. Allow
60 seconds for the display firmware to cycle through start-up diagnostic routines.
2. Open Internet Explorer and enter an address of http://192.168.1.24.
3. From navigation tree on the right in the image below, select setup and then network settings.
1. Enter the new IP address, subnet mask and gateway address as needed. Click on Update IP Settings
to update the settings and then click on System Restart to complete the update.
Navigation Tree
System restart required
to complete the update.
Click here to upload
the new settings.