System-10 Dual Network Interface Installation Guide
Page 22
2.6 Binary Value(s)
Property
Default Value
Read-only or Writable
Object Identifier
Binary value 11 to binary value 15
Read-only
Object Name
Various
Read-only
Object Type
Binary-value
Read-only
Present Value
0
Writable
Description
Binary-value,# Name
Read-only
Status Flags
(F,F,F,F)
Read-only
Event State
normal
Read-only
Reliability
No-fault-detected
Read-only
Out-of-Service
FALSE
Writable
Active Text
Active
Read-only
Inactive Text
Inactive
Read-only
Priority Array
(NULL, NULL, NULL, NULL, NULL, NULL, NULL, NULL,
NULL, NULL, NULL, NULL, NULL, NULL, NULL, NULL)
Read-only
Relinquish Default
0
Read-only
Description
Various
Writable
Binary Value Objects
Object Identifier
Description
Notes
Binary value 11
Zero Mode 1 Energy Total
Changing this property from
the (0) inactive state to the
(1) active state will reset
the total to zero. (Must be
priority 8 manual operator).
Binary value 12
Zero Mode 1 Volume Total
Binary value 13
Zero Mode 2 Energy Total
Binary value 14
Zero Mode 2 Volume Total
Binary value 15
Zero Mode Aux Input Total