ONEAC Sinergy UPS User Manual
35
NOTE: for electrical specifications see “ONEAC Sinergy UPS (S Series) North America” on page 30.
Table 9. Sinergy Series Rackmount Technical Data for North American Models
Type
S700A-RM
S1000XA-RM
S2000XA-RM
S3000XA-RM
Dimensions
Unit dimensions - WxHxD - in. (mm)
19 x 3.5 x 17.6
(483 x 87 x 448)
19 x 3.5 x 17.6
(443 x 87 x 448)
19 x 3.5 x 18.8
(443 x 87 x 478)
19 x 3.5 x 18.8
(443 x 87 x 478)
Body dimensions - WxHxD - in. (mm)
16.1 x 3.5 x 16.1
(410 x 87 x 410)
16.1 x 3.5 x 16.1
(410 x 87 x 410)
16.1 x 3.5 x 17.3
(410 x 87 x 441)
16.1 x 3.5 x 17.3
(410 x 87 x 441)
Weight - lbs (kg)
33 (15)
40 (18)
27 (12)
30 (13.5)
Operating Data
Ambient temperature
+50°F to 104°F (+10°C to +40°C)
5000 ft to 10000 ft: 50°F to 95°F (1500 m to 3000 m: +10°C to +35°C)
Storage temperature
+5°F to +104°F (-15°C to +40°C)
Relative Humidity
20% to 90%, non-condensing
Type of cooling
Fan
Safety class
UL1778
RFI class
FCC part 15 Class A
Efficiency
> 83%
> 83%
> 83%
> 83%
Noise level
42 dBa
42 dBa
50 dBa
50 dBa
Installation
Mains connections
5-15P
5-15P
L5-20P
L5-30P
Electrical load (output)
(3) 5-15R
(3) 5-15R
(2) 5-20R
(1) L5-30R
Minimum fuse protecting of mains
10 A
15 A
20 A
30 A
Battery pack - external
—
SBP1000-RM
SBP3000-RM
SBP3000-RM
Battery voltage
—
36 V
96 V
96 V
Net weight (kg)
—
47.5 (21.5)
59.5 (27)
59.5 (27)
Dimensions
—
same as UPS