ONEAC Sinergy UPS User Manual
31
Common Data
Electrical safety
UL1778
Radio interference level
FCC Part 15 Class A
Interference immunity
IEC 801-2,level 4 / IEC 801-3,level 3;
IEC 801-4,level 4 / IEC 801-5,level 2)
Efficiency
> 83%
Protection class
IP 20
Cooling
Fan
Noise level mains operation
< 41 dBa
< 41 dBa
< 50 dBa
< 50 dBa
Noise level battery operation
< 45 dBa
<45 dBa
< 50 dBa
<50 dBa
Operating temperature (ambient)
+ 50°F to +105°F (10°C to + 40°C)
recom59°F to +89°F (+15°C to + 32°C)
Storage temperature
+5°F to +104°F (-15°C to +40°C)
Relative humidity
20% to 90%,non-condensation
Altitude
max. 10,000 ft. (3000m),
above 5,000 ft. (1500m) max ambient temperature = 95°F (35 °C)
Mechanical Data
UPS
Weight - lbs. (kg)
28.6 (13)
35.3 (16)
75 (34)
75 (34)
Dimensions - HxWxD in. (mm)
8.9 x 5.7 x 16 (225 x 145 x 405)
13.8 x 7.9 x 18.5 (350 x 200 x 470)
Battery extension
Type
None
SBP1000
SBP3000
SBP3000
Weight lbs (kg)
None
42 (19)
106 (48)
106 (48)
Dimensions - HxWxD in. (mm)
None
8.9 x 5.7 x 16
(225x145x405)
13.8 x 7.9 x 18.5
(350 x 200 x 470)
Signals
Visual
LED-indication at the front side
Audible
Acoustical alarm
Communications
RS232 interface
Alarm co5V...+12 V
Signal input +5V...+12 V
Ethernet (optional)
Table 7. ONEAC Sinergy UPS (S Series) North America
UPS Model
S700A
S1000XA
S2000XA
S3000XA