Section 4.  Installation

INSTALLATION REQUIREMENTS

Generator set installations must conform to local building

codes, fire ordinances, and other local, state and federal

regulations.

Installation requirements include:

Level mounting surface

Adequate cooling air

Adequate fresh induction air

Discharge of circulated air

Discharge of exhaust gases

Electrical connections

Fuel connections

Accessibility for operation and servicing

Isolation from vibration 

Minimal noise levels

For more detailed installation instructions, consult Onan

Application Manual T-030, or contact an authorized

Onan service representative.

  Incorrect installation, service, or parts

replacement can result in severe personal injury,

death, and/or equipment damage.  Service person-

nel must be qualified to perform electrical and me-

chanical component installations and service.  In-

stallation must comply with all state and local codes.

GENERATOR SET LOCATION

Provide a location for the generator set that is dry, clean,

dust-free, well-ventilated, and protected from the

weather.

The left side of the set, where generator air is discharged,

requires 3 inches (76 mm) clearance from the wall, so the

set can rock on its mounts.  There should be at least 24

inches (610 mm) clearance around all other sides for

service access.

MOUNTING

A permanent genset installation must have a sturdy, level

mounting base of concrete, heavy wood or structural

steel. This base should be raised if possible, for easier oil

changing and set operation.  The set may be bolted into

position.

On all installations, assemble the mounting cushions,

washers and spacer bushing carefully.  The spacer bush-

ing prevents compression of the snubber (upper rubber

cushion). Place the cushions (Figure 4-1) under the en-

gine and generator mounting feet.  Use cushions with a

higher number (part number is shown on cushion) on the

heavier generator end.  Space the mounting bolts in the

floor or the base with distances between hole centers as

shown in Figure 4-2 for either the DJB or the DJE.

  The oil filter can be punctured easily by

the end of the mounting bolt.  For this reason, pro-

vide at least 1/2-inch (12.7 mm) clearance between

the oil filter and the end of the mounting bolt, to avoid

puncturing the filter.

CS1370-1

FIGURE 4-1.  MOUNTING CUSHION INSTALLATION

CARRIAGE

BOLT

SQUARE

NUT

LOCK

WASHER

FLAT

WASHER

SNUBBER

GENERATOR

OR OIL BASE

MOUNTING

FOOT

CUSHION

MOUNTING SPACER

BUSHING

FLAT

WASHER

1/16"

(1.59 mm)

Содержание DJB

Страница 1: ...967 0121 2 91 Printed in U S A Electric Generating Sets GenSets Operator s Manual...

Страница 2: ...lectrical Connections 4 7 Balancing Loads 4 8 Grounding 4 11 Switchboard 4 11 Reconnectible Generators 4 11 Battery Connections 4 11 Optional Alarm 4 12 Remote Start Stop Switch Optional 4 12 5 OPERAT...

Страница 3: ...s 7 1 Governor Linkage 7 2 Crankcase Breather Tube 7 2 Crankcase Breather 7 2 Cooling System Maintenance 7 2 Fuel Pump Sediment Bowl 7 3 Air Cleaners 7 3 Contractor Model Air Cleaner 7 3 Optional Oil...

Страница 4: ...n become caught in moving parts Jewelry can short out electrical contacts and cause shock or burning If adjustment must be made while the unit is running use extreme caution around hot manifolds movin...

Страница 5: ...OR DIESEL For the name of your local Cummins Onan or Onan only distributor in the United States or Canada call 1 800 888 ONAN this automated service uses touch tone phones only By entering your area...

Страница 6: ...ts BCI Group Cranking Performance Amp Hr Capacity Range Size at 0 F 17 C 20 hour rate 32 F 0 C and warmer 2 6 1 450 amps 105 0 F 17 C and warmer 2 6 2 560 amps 135 25 F 32 C and warmer 2 6 5D 800 amps...

Страница 7: ...Cranking Performance Amp Hr Capacity Range Size at 0 F 17 C 20 hour rate 32 F 0 C and warmer 2 6 1 450 amps 105 0 F 17 C and warmer 2 6 2 560 amps 135 25 F 32 C and warmer 2 6 5D 800 amps 190 GENERAT...

Страница 8: ...CONTROL PANEL ES1972C START STOP SWITCH KNOCKOUT PLUGS FOR OPTIONAL CONTROLS FIELD BREAKER DC AMMETER FUSE PREHEAT SWITCH Optional Features found on Housed Units AC Voltmeter Monitors output voltage...

Страница 9: ...is equipped with a high air temperature cutoff switch HATCO to shut down the engine if engine tem perature rises above 375 F 15 F 190 5 C AC Control With Meters The AC control panel has a voltmeter am...

Страница 10: ...RS OIL DRAIN OIL FILTER COOLING AIR IN SPEED ADJUSTMENT GOVERNOR SENSITIVITY ADJUSTMENTS AIR CLEANER FIELD BREAKER PREHEAT SWITCH G1246 2 FIGURE 3 4 DJE GENERATOR SET CONTRACTOR VERSION START SWITCH F...

Страница 11: ...inches 76 mm clearance from the wall so the set can rock on its mounts There should be at least 24 inches 610 mm clearance around all other sides for service access MOUNTING A permanent genset instal...

Страница 12: ...this set See Figure 4 3 DJE Pressure Cooling The pressure cooled DJE needs an inlet vent with an unrestricted opening of at least 3 1 2 square feet 3252 cm2 for variables Section 2 of this manual SPE...

Страница 13: ...escape Use only original equipment replacement parts when servicing the exhaust system Unauthor ized modifications will also void the warranty and cancel the UL Listing CSA Certification Liability fo...

Страница 14: ...TO LOAD AUTOMATIC TRANSFER SWITCH MAIN FUSE AND SWITCH MUFFLER DUCT TO REMOVE HEATED ENGINE AIR NOTE If revolving field type unit is installed in smaller than approximately 384 cu ft 11 m3 compartment...

Страница 15: ...ILING AUTOMATIC LOAD TRANSFER CONTROL METER INCOMING SERVICE MAIN FUSE AND SWITCH FLEXIBLE SECTION FLEXIBLE FUEL LINE FUEL RETURN LINE BATTERIES CANVAS SECTION DUCT TO REMOVE HEATED ENGINE AIR AUTOMAT...

Страница 16: ...r either the DJB or DJE generator set Use an approved flexible fuel line next to the engine Die sel engines require a fuel supply line and a separate fuel return line Install the fuel supply line from...

Страница 17: ...out a supply line shutoff valve a ruptured pump diaphragm could cause oil dilution fuel loss and fuel leakage to the crankcase 3 If the maximum fuel lift must be exceeded on any in stallation consult...

Страница 18: ...en the generator and the load If a test run indicates the wrong rotation of 3 phase motors in the load circuit switch the connections at any two of the generator termi nals Electrical shock can cause...

Страница 19: ...nal current exceeds the nameplate rating of the generator If no 3 phase output is used usable 1 phase output is 2 3 of 3 phase kVA 3 Phase 4 Wire Wye Connected Set The 3 phase 4 wire connection produc...

Страница 20: ...4 10 FIGURE 4 12 GENERATOR WIRING AND CONNECTION DIAGRAMS B200...

Страница 21: ...d on the switchboard 3 Connect one ungrounded hot load wire to the un used terminal on each circuit breaker 4 On sets that generate more than one voltage ex ample 120 240 wire the voltmeter to indicat...

Страница 22: ...be damaged almost in stantly if the battery charging circuit is shorted be tween resistor R21 and the B1 end of the charging winding Make certain that battery polarity is cor rect to avoid damaging o...

Страница 23: ...IRE SIZE DISTANCE 18 1 02 mm to 65 ft 20 m 16 1 29 mm to 100 ft 31 m 14 1 63 mm to 150 ft 47 m 12 2 05 mm to 280 ft 87 m ES1970C REMOTE CONTROL TERMINAL BLOCK AT GENERATOR MOMENTARY CONTACT SWITCHES S...

Страница 24: ...ting the generator set Oil Recommendations The use of quality engine lubricating oils combined with appropriate oil drain and filter change intervals are criti cal factors in maintaining engine perfor...

Страница 25: ...ON PUMP RETURN LINE FITTING DJB FUEL SYSTEM BLEEDING DJE FUEL SYSTEM BLEEDING FS1854C WORK TRANSFER PUMP PRIMING LEVER UNTIL FUEL FLOWS FROM RETURN LINE OF INJECTION PUMP RETURN LINE Recommended Fuel...

Страница 26: ...be nec essary to maintain preheating for two minutes after the engine starts to obtain firing or smooth out cylin ders especially at no load or light loads NOTE When remotely starting the set the swit...

Страница 27: ...rect its cause Press the reset button on the control panel before restarting Hot oil can cause severe personal in jury Do not check the oil level while the generator set is running wait until the gene...

Страница 28: ...oil flows freely 2 Use fresh fuel Protect against moisture condensa tion 3 Keep fuel system clean and batteries in a well charged condition 4 Partially restrict cool air flow but use care to avoid ov...

Страница 29: ...muffler exhaust line etc and repair as necessary Exhaust gases contain carbon monoxide which may cause severe personal in jury or death Before operating the generator set make certain the exhaust line...

Страница 30: ...INCH 51 mm GOVERNOR The governor controls engine speed On a 4 pole gen erator engine speed equals frequency multiplied by 30 Thus 1800 rpm generates 60 hertz Preferred engine speed does not vary more...

Страница 31: ...Batteries present the hazard of explo sion which can result in severe personal injury Be cause batteries produce explosive gas do not smoke or allow any flame sparks or arc producing devices in the ba...

Страница 32: ...valve clearance with the locknut which secures the rocker arm to the cyl inder head see Figure 6 4 Loosen this locknut to increase clearance tighten it to reduce clearance FIGURE 6 4 VALVE CLEARANCE A...

Страница 33: ...the starting batteries at least every two weeks Make certain that connections are clean and tight A light coating of non conductive grease will retard corrosion at terminals Add distilled water t o ke...

Страница 34: ...turer s recommendations before using any lubricants or solvents near the ball joints Fumes from this cleaner may present the hazard of fire or explosion which can cause se vere personal injury or deat...

Страница 35: ...tion remove hose clamp breather hose breather cap clamp and insulator halves to release breather cap and valve assembly Figure 7 4 Wash cap valve assembly and baffle in suitable solvent Dry and reinst...

Страница 36: ...place FIGURE 7 5 FUEL PUMP SEDIMENT BOWL FS1115 FUEL PUMP AND FILTER BODY FILTER GASKET BOWL AIR CLEANERS After every 50 hours of operation remove and clean the filter element Figure 7 6 After washing...

Страница 37: ...7 5 FIGURE 7 7 DJE CONTRACTOR MODEL AIR CLEANER FS1853C COVER BAFFLE ELEMENT THUMBSCREW CLAMP DUST CUP PRE CLEANER...

Страница 38: ...ative cable first before beginning any maintenance work on the engine generator control panel automatic transfer switch or associated wir ing Stop the engine and drain the crankcase oil while the en g...

Страница 39: ...9 OIL LEVEL INDICATOR LS1181 ALWAYS REPLACE CAP TIGHTLY OR OIL LEAKAGE MAY OCCUR CAP AND OIL LEVEL INDICATOR KEEP CRANKCASE OIL AT THIS LEVEL NEVER OPERATE ENGINE WITH OIL BELOW THIS LEVEL FULL LOW O...

Страница 40: ...he exhaust system audibly and visually each day or each time the generator is started whichever is sooner With the generator set running momentarily open the ac cess cover to inspect the muffler Shut...

Страница 41: ...adjust valve clearance after first 50 hours on new and over hauled engines and then adjust valve clearance each 500 hours thereafter 8 Inspect exhaust system Inspect generator set Check fuel supply se...

Отзывы: