background image

OnLine Power  

 

 (6002-1646) REV.

X8

 

38 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 

 
 
 
 
 
 
 
 

 

 + 

 

 + 

 

 + 

 

 + 

#8 

#7 

#6 

#5 

 

 + 

 

 + 

 

 + 

 

 + 

#4 

#3 

#2 

#1 

BATT C.B 

96VDC 

UPS CAB 

TB3 

BATT 
C.B 

2ND 
LEVEL 

1ST 
LEVEL 

BATTERY CABINET "B" 

B CABINET BATTERY (QTY: 8 ) SYSTEM 

Содержание Fire Alarm Back-up UPS1481 UNIT

Страница 1: ...User s Manual Fire Alarm Back up UPS1481 UNIT Emergency Power Systems Doc 6002 1646 Revision X8 Installation and Operating Documentation...

Страница 2: ...ve equipment and critical applications Our customers both new and long time continue to enjoy security and peace of mind as they realize what it means to When the lights go out we turn on One of our g...

Страница 3: ...e them to or allow them to be used by any person not currently a On Line Power employee or an employee of the recipient having a need to know without the express written consent of On Line Power and f...

Страница 4: ...should not be modified and or used for any application other than for that which it was designed Optional equipment not described in the sales literature or this manual should not be installed withou...

Страница 5: ...1 REMOTE SIGNALING CONNECTIONS 15 2 4 STORAGE 16 SECTION 3 OPERATION 18 3 1 START UP PROCEDURES 18 3 2 OPERATION 19 3 2 1 TURN ON THE Fire Alarm Back up UPS1481 19 3 2 2 TURN OFF THE Fire Alarm Back u...

Страница 6: ...2005 RELEASE FOR PRODUCTION X3 OCT 30 2006 UPDATE X4 NOV 03 2006 UPDATE P11 P29 X5 MAY 21 2007 UPDATE X6 JUN 21 2007 UPDATE X7 Nov 15 2007 Per UL Review X8 MAY 30 2008 PER UL REVIEW LIST OF EFFECTIVE...

Страница 7: ...m the Fire Alarm Back up UPS1481 contains a 160 alpha numeric display and touch pad UPS status event history and operating parameters such as input output voltage are readily available to the operator...

Страница 8: ...mer when used This switch shuts off in case of a problem or failure within the UPS and transfers the load directly to the utility input via bypass static switch It maintains it s status opposite to th...

Страница 9: ...ed maintenance free batteries The batteries provide emergency power during power outages The battery bank includes a breaker for overcurrent protection and DC disconnect Input Contactor The input cont...

Страница 10: ...OnLine Power 6002 1646 REV X8 4...

Страница 11: ...DOWN BATT CHARGER Q3 4 Q5 6 POWER FACTOR CONTLR INVERTER Q1 Q2 A1 POWER BOARD ASSY L2 OUTPUT FILTER SCR DRIVER T2 FAX XFMR FANS BYPASS SCR BYPASS 1 2 OUTPUT C B OUTPUT XFMR T1 7 ONLY USED FOR MULTIPL...

Страница 12: ...stalled in inside of the UPS 1 3 2 CB1 INPUT TB1 CUSTOMER WIRES TO CB1 PROTECTOR CUSTOMER S CONNECTION TERMINAL BLOCK ILLUSTRATION 1 6 From External Battery Cabinet 1 HOT 2 HOT N 3 GND 1 OV 2 120V 3 O...

Страница 13: ...UT AND OUTPUT VOLTAGE UNIT WITHOUT OUTPUT XFMR 1 3 4 TB2 7 6 5 2 N C N C OUTPUT CB GND N H TO CUSTOMER LOAD 120V OUT OPTION UPS CABINET B A C PB2 1 1 120V IN OUTPUT UNIT 2 240V IN OUTPUT UNIT 1 3 4 7...

Страница 14: ...0 OUTPUT UNIT 1 3 4 7 6 5 2 OUTPUT CB TO CUSTOMER LOAD OPTION FOR EACH OUTPUT VOLT B A C PB2 1 TB2 8 9 11 12 13 14 1 2 4 5 7 6 240V 120V 157V 120V 88V 0V 0V 120V 240V 120V 120V H1 H2 N CONNECT TO TB2...

Страница 15: ...nual supplied with each piece of equipment The device s nameplate should list the electrical requirements of the device in some or all of the following units nominal voltage current VA or kVA and watt...

Страница 16: ...e are some types of loads which require an excessive inrush current when first turned on or at other times during its operation The capacity of the Fire Alarm Back up UPS1481 may need to be greater th...

Страница 17: ...uld be provided for service access OPERATING ENVIRONMENT AMBIENT TEMPERATURE 0 C to 49 C OPERATING ALTITUDE 1 829 M 6 000 FT DERATE 10 FOR EACH ADDITIONAL 305 M 1 000 F UP TO 2 744 m 9 000 FT RELATIVE...

Страница 18: ...120 240 21 00 240 120V 57A 10 9 WR7 5B58FPT1 7 5 208 44 120 240 62 5 120 120V 86A 10 10 WR7 5D58FPT1 7 5 240 41 120 240 31 3 240 120V 86A 10 12 WR010B58FPT1 70 0 208 44 120 240 83 0 120 192V 71A 16 13...

Страница 19: ...D58FPT1 240 120 240V 9100 1319 081UL 9100 1312 11 11 12 WR010B58FPT1 208 120 240V 9100 1319 101UL 9100 1312 11 1680 139 2025 772 13 WR010D58FPT1 240 120 240 9100 1319 105UL 9100 1312 11 14 15 WR012B58...

Страница 20: ...e used to remove the Fire Alarm Back up UPS1481 from its shipping pallet Before placing the Fire Alarm Back up UPS1481 onto the mounting bolts or leveller where it will be installed the conduit knocko...

Страница 21: ...up UPS1481 includes the feature of providing dry relay contacts for remote signaling capabilities Signals available of remote annunciation are UTILITY FAILURE This is a normally open contact which clo...

Страница 22: ...Pin 1 4 6 7 9 no connection Pin 2 Receive Pin 3 Transmit Pin 5 GND 2 4 Storage The Fire Alarm Back up UPS1481 Series can be placed in storage while not in use Provide a protected environment which me...

Страница 23: ...When the UPS is unpacked and first connected to an AC power source recharge batteries as follows 1 Unlock and remove the front panel by pushing it up and out pull both the side panel up and out 2 Visu...

Страница 24: ...voltage appearing on the input terminal block is 120 240 VAC and is same as on nameplate lithe voltage is not same as on nameplate approximately do not proceed any further Contact On Line Power at 80...

Страница 25: ...k up UPS1481 should be running on its internal batteries Verify that the LCD panel displays such Verify that the Battery Charger is OFF in LCD panel Note Be sure to release the switch after the test s...

Страница 26: ...voltage 4 Battery charger The battery charger converts AC power into regulated DC power to charge and to maintain the charge on the battery bank The charger is fully automatic with a current limiting...

Страница 27: ...larm Back up UPS1481 is running and Switch SW2 is pushed and held in the Fire Alarm Back up UPS1481 will automatically transfer to battery operation The Fire Alarm Back up UPS1481 will continue to run...

Страница 28: ...OnLine Power 6002 1646 REV X8 22 3 4 COMPONENT S LOCATION LIST...

Страница 29: ...OnLine Power 6002 1646 REV X8 23 COMPONENT S TABLE...

Страница 30: ...OnLine Power 6002 1646 REV X8 24...

Страница 31: ...OnLine Power 6002 1646 REV X8 25 3 4 ITEM 18 CONTINUED...

Страница 32: ...0x90 30x90 40x120 60x90 60x90 Cabinet A A B A B A B A B A C A C A C A B C A 2C A B 2C A B 2C orA A orA A orA A orA A Minutes 240 240 240 240 240 240 240 240 240 240 240 N A Batt A H 8x50 8x90 8x100 8x...

Страница 33: ...AIC OLP P N 2025 794 12 5 1750 Amps 120 VAC 2 Pole 10 KAIC OLP P N 2025 468 80 Amps 240 VAC 2 Pole 10 KAIC OLP P N 2025 795 15 200 Amps 120 VAC 2 Pole 65 KAIC OLP P N 2025 541 100 Amps 240 VAC 2 Pole...

Страница 34: ...P P N 2025 794 12 5 N A 90 Amps 240 VAC 2 Pole 10 KAIC OLP P N 2025 796 15 N A 125 Amps 240 VAC 2 Pole 65 KAIC OLP P N 2025 759 TABLE B 4 Input Breaker Ampacity hIGH KAIC Input Voltages KVA 120 Vac 24...

Страница 35: ...t LCD panel lights up and displays If LCD display panel is not lit unit has a problem Contact factory service at 1 800 PWR SRVC at OnLine Power SCREEN A The screen appears as below It may show 1 UPS N...

Страница 36: ...output transformer T1 120 VAC typically when T1 is used 5 Indicates input volts and Amps 6 Indicates internal DC buss condition for factory use 7 Indicates battery voltage The current in Amps indicate...

Страница 37: ...OnLine Power 6002 1646 REV X8 31...

Страница 38: ...ck OUTPUT RATING KVA KW 3 0 5 0 7 5 10 12 5 15 VOLTAGE VAC 120 120 240 120 120 240 120 240 120 240 120 240 120 240 VOLTAGE REGULATION 3 No Load to Full Load 3 High Line to Low Line FREQUENCY Hz 60 Hz...

Страница 39: ...ximum 1 25 Amperes Maximum 30 Watts 50 VA Maximum INTERFACE CONNECTION Hard Wired Terminal Block ENVIRONMENTAL USRGE WITHSTANDABILITY ANSI C62 41 1980 Categories A B OPERATING TEMPERATURE Meets NEMA R...

Страница 40: ...OnLine Power 6002 1646 REV X8 34...

Страница 41: ...OnLine Power 6002 1646 REV X8 35...

Страница 42: ...NET B BATT C B 6 7 5 4 3 2 1 8 9 10 1 2 120VDC BUSS UPS CAB TB3 BATT C B 3 B CABINET BATTERY QTY 10 SYSTEM 2ND LEVEL 1ST LEVEL 6 7 5 4 3 2 1 8 9 10 15 14 13 12 11 16 3RD LEVEL 4TH LEVEL BATT C B 1 2 U...

Страница 43: ...11 2ND LEVEL 1ST LEVEL 3RD LEVEL 17 18 16 19 20 4TH LEVEL BATT C B 1 2 UPS CAB TB3 BATT C B 3 3 VDC BUSS C CABINET BATTERY QTY 20 SYSTEM 8 7 6 5 4 3 2 1 1 2 3 TB3 BATT C B 2ND LEVEL 1ST LEVEL 96VDC 19...

Страница 44: ...OnLine Power 6002 1646 REV X8 38 8 7 6 5 4 3 2 1 BATT C B 1 2 96VDC UPS CAB TB3 BATT C B 3 2ND LEVEL 1ST LEVEL BATTERY CABINET B B CABINET BATTERY QTY 8 SYSTEM...

Страница 45: ...OnLine Power 6002 1646 REV X8 39...

Страница 46: ...OnLine Power 6002 1646 REV X8 40...

Страница 47: ...OnLine Power 6002 1646 REV X8 41...

Страница 48: ...OnLine Power 6002 1646 REV X8 42...

Страница 49: ...OnLine Power 6002 1646 REV X8 43...

Страница 50: ...OnLine Power 6002 1646 REV X8 44...

Отзывы: