OnLine Power
(6002-1646) REV.
X8
32
APPENDIX D: SPECIFICATION
POWER RATING (KW)
3.0
5.0
7.5
10
12.5
15
VOLTAGE
(VAC) INPUT
Single Phase,
120/208/240
Single Phase, 240/208VAC
MAXIMUM CURRENT
40/19/16
58/30/28
41/36
58/50
69/60
83/72
TOLERANCE
+10% to -15%
FREQUENCY (Hz)
60 +/- 3%
POWER FACTOR
0.98 to 1.0 (Typical)
OVERCURRENT PROTECTION
Electronic / Circuit Breaker
NUMBER OF WIRES
2 Wires plus Ground
POWER CONNECTION
Hard Wired (Terminal Block)
OUTPUT
RATING (KVA/KW)
3.0
5.0
7.5
10
12.5
15
VOLTAGE (VAC)
120/120/240 120/120/240 120/240 120/240 120/240 120/240
VOLTAGE REGULATION
+/-3% No Load to Full Load; +/-3% High Line to Low Line
FREQUENCY (Hz)
60 Hz +/-0.25 Hz (When on Inverter)
WAVESHAPE
Sine Wave
HARMONIC DISTORTION
<5% THD; <3% Single Harmonic
CREST FACTOR
Up to 3 to 1
POWER FACTOR
1.0PF
STEADY-STATE CURRENT
25/12.5
42/20.8
62.5/31.3
83.3/41.7
104/52
125/62.5
OVERLOAD
125 % for One (1) minutes, surge 150 %
PROTECTION
Electronic / Circuit Breaker
NOISE REJECTION
-120 kB Common Mode; -60 kB Normal Mode
NUMBER OF WIRES
2 Wires plus Ground
POWER CONNECTION
Hard Wired (Terminal Block)
Содержание Fire Alarm Back-up UPS1481 UNIT
Страница 10: ...OnLine Power 6002 1646 REV X8 4...
Страница 28: ...OnLine Power 6002 1646 REV X8 22 3 4 COMPONENT S LOCATION LIST...
Страница 29: ...OnLine Power 6002 1646 REV X8 23 COMPONENT S TABLE...
Страница 30: ...OnLine Power 6002 1646 REV X8 24...
Страница 31: ...OnLine Power 6002 1646 REV X8 25 3 4 ITEM 18 CONTINUED...
Страница 37: ...OnLine Power 6002 1646 REV X8 31...
Страница 40: ...OnLine Power 6002 1646 REV X8 34...
Страница 41: ...OnLine Power 6002 1646 REV X8 35...
Страница 45: ...OnLine Power 6002 1646 REV X8 39...
Страница 46: ...OnLine Power 6002 1646 REV X8 40...
Страница 47: ...OnLine Power 6002 1646 REV X8 41...
Страница 48: ...OnLine Power 6002 1646 REV X8 42...
Страница 49: ...OnLine Power 6002 1646 REV X8 43...
Страница 50: ...OnLine Power 6002 1646 REV X8 44...