4-4 Operation Parameter Setting
4-9
4-4-3 Response Delay Time
When several controllers are connected to a host device through RS-485 etc. (commercial 232C/485 converter is required), RS-485
switches into receiving after data string is sent. Switching time varies depending on a converter. So, if a response from the controller is
fast, the communication cannot be executed correctly.
By specifying the Response Delay time, the response start time can be changed.
* Actual time from the transmission of command to the start of response is internal process time (a minimum time is 0 ms) of the con-
t Response Delay time (specified time).
* The default value is 0 ms.
Setting Range
0 to 9999 ms.
Correct Usage
For how to use the operation parameter setting (SP) command, refer to the description of "5-8-6 Parameter Setting
(SP)".
Host
→
Controller
Host
←
Controller
External input
Response
Internal process time
Response Delay time
Command