![Omron Sysmac NY512-1300 Скачать руководство пользователя страница 416](http://html.mh-extra.com/html/omron/sysmac-ny512-1300/sysmac-ny512-1300_user-manual_742451416.webp)
Appendices
A-30
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
•
Transferring all data
1
Establish an online connection between the computer and the Controller and then select
Transfer
-
To Controller
from the Controller Menu. (Or, click the
Button on the Toolbar.)
2
The
Transfer to Controller
Dialog Box is displayed.
Clear the selection of the
Do not transfer the EtherNet/IP connection settings (i.e., tag data link
settings)
Check Box then click the
Execute
Button.
Precautions for Correct Use
Precautions for Correct Use
To transfer only the connection settings, execute Transfer from the EtherNet/IP Connection Set-
ting Tab Page.
The connection settings are not transferred from the Synchronization Window, the Transfer to
Controller Dialog Box, and the Transfer from Controller Dialog Box, even if you clear the
Do not
transfer the connection setting
Check Box, as long as the data in the computer and in the Con-
troller is the same.
Transferring Only the EtherNet/IP Connection Settings
You can transfer tag sets and connections to the EtherNet/IP devices.
1
Establish an online connection with the Controller.
2
Click the
Transfer to Controller
or
Transfer from Controller
Button in the EtherNet/IP Con-
nection Setting Tab Page.
The tag settings and connection settings set at that time are transferred to the Controller con-
nected online.
Содержание Sysmac NY512-1300
Страница 290: ...9 Socket Service 9 32 NY series Industrial Panel PC Industrial Box PC Built in EtherNet IP Port User s Manual W563 ...
Страница 310: ...10 FTP Server 10 20 NY series Industrial Panel PC Industrial Box PC Built in EtherNet IP Port User s Manual W563 ...
Страница 324: ...11 FTP Client 11 14 NY series Industrial Panel PC Industrial Box PC Built in EtherNet IP Port User s Manual W563 ...
Страница 452: ...Appendices A 66 NY series Industrial Panel PC Industrial Box PC Built in EtherNet IP Port User s Manual W563 ...
Страница 453: ...Index 1 NY series Industrial Panel PC Industrial Box PC Built in EtherNet IP Port User s Manual W563 I Index ...
Страница 459: ......