8 CIP Message Communications
8-56
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
Response Codes
CIP
status
Meaning
Add
status
Cause
00
SUCCESS
---
The service ended normally.
02
RESOURCE_UNAVAILABLE
---
The internal processing buffer is not
available.
04
PATH_SEGMENT_ERROR
---
The request path specification is not cor-
rect.
05
PATH_DESTINATION_UNKNOWN
---
The link was followed to the end, but the
variable was not found.
0C
OBJECT_STATE_CONFLICT
8010
Downloading, starting up
8011
There is an error in tag memory.
13
NOT_ENOUGH_DATA
---
The data length was too short for the
specified service.
15
TOO_MUCH_DATA
---
The data length was too long for the
specified service.
1F
VENDOR_SPECIFIC_ERROR
0102, 2103 An attempt was made to write a constant
or read-only variable.
0104, 1103
The specified address and size exceed
a segment boundary.
8001
An internal error occurred. (An informa-
tion inconsistency was detected in the
interface in the Module.)
8007
An inaccessible variable was specified.
8029
A region that all cannot be accessed at
the same time was specified for
Simple-
DataSegment
.
8031
An internal error occurred. (A memory
allocation error occurred.)
20
INVALID_PARAMETER
8009
A segment type error occurred.
800F
There is an inconsistency in data length
information in the Request Data.
8017
More than one element was specified for
a variable that does not have elements.
8018
Zero elements or data that exceeded the
range of the array was specified for an
array.
8021
A value other than 0 or 2 was specified
for an AddInfo area.
8022
The data type that is specified in the
request service data does not agree with
the tag information. The AddInfo Length
in the request service data is not 0.
8023
An internal error occurred. (An illegal
command format was used.)
8024
An internal error occurred. (An illegal
command length was used.)
8025
An internal error occurred. (An illegal
parameter was used.)
8027
An internal error occurred. (A parameter
error occurred.)
8028
•
An attempt was made to write an out-
of-range value for a variable for which
a subrange is specified.
•
An attempt was made to write an
undefined value to an enumeration
variable.
Содержание Sysmac NY512-1300
Страница 290: ...9 Socket Service 9 32 NY series Industrial Panel PC Industrial Box PC Built in EtherNet IP Port User s Manual W563 ...
Страница 310: ...10 FTP Server 10 20 NY series Industrial Panel PC Industrial Box PC Built in EtherNet IP Port User s Manual W563 ...
Страница 324: ...11 FTP Client 11 14 NY series Industrial Panel PC Industrial Box PC Built in EtherNet IP Port User s Manual W563 ...
Страница 452: ...Appendices A 66 NY series Industrial Panel PC Industrial Box PC Built in EtherNet IP Port User s Manual W563 ...
Страница 453: ...Index 1 NY series Industrial Panel PC Industrial Box PC Built in EtherNet IP Port User s Manual W563 I Index ...
Страница 459: ......