EtherCAT Connection Procedure
11
7.2. Kashiyama Dry Vacuum Pump Setup
Set up the Kashiyama Dry Vacuum Pump.
7.2.1. Hardware Settings
Set the hardware switches on the Dry Vacuum Pump and connect the cable.
Precautions for Correct Use
Make sure the power supply is OFF before setting up. If it is ON, the settings described in the
following steps and subsequent procedures may not be applicable.
1
Make sure Dry Vacuum Pump is
powered OFF.
*For information on the power
supply connection to Dry
Vacuum Pump, refer to the
manuals of your Dry Vacuum
Pump.
2
Check the positions of the
hardware switches and
connectors on Dry Vacuum
Pump by referring to the figure
on the right
3
Set ID Selector as follows:
x100:
0
x10:
0
x1:
1
*The node address is set to 1.
ID Selector
EtherCAT Connector
x100
x10
x1
1
0
0
ID Selector