* 1
Total of 110 mm with mounting brackets.
* 2
Excluding cables.
* 3
Use the external power supply to power input devices. Do not use it to drive output devices.
* 4
This is the rated value for the maximum system configuration. Use the following formula to calculate power consumption for CPU Units with
DC power.
Formula: DC power consumption = (5V current consumption
✕
5 V/70% (internal power efficiency) + 24V current consumption)
✕
1.1(current
fluctuation factor)
The above calculation results show that a DC power supply with a greater capacity is required.
Type
AC power supply models
DC power supply models
Model
CP1E-
@@@
D
@
-A
CP1E-
@@@
D
@
-D
Enclosure
Mounted in a panel
Dimensions (H × D × W)
CPU Unit with 10 I/O points (CP1E-E10D
@
-
@
): 90mm
*
1 ×85mm
*
2 × 66 mm
CPU Unit with 14 or 20 I/O points (CP1E-
@
14D
@
-
@
/
@
20D
@
-
@
): 90mm
*
1 × 85mm
*
2 × 86 mm
CPU Unit with 30 I/O points (CP1E-
@
30D
@
-
@
): 90mm
*
1 × 85mm
*
2 × 130 mm
CPU Unit with 40 I/O points (CP1E-
@
40D
@
-
@
): 90mm
*
1 × 85mm
*
2 × 150 mm
CPU Unit with 60 I/O points (CP1E-N60D
@
-
@
): 90mm
*
1 ×85mm
*
2 × 195 mm
CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D
@
-
@
): 90mm
*
1 ×85mm
*
2 × 130 mm
Weight
CPU Unit with 10 I/O points (CP1E-E10D
@
-
@
): 300g max.
CPU Unit with 14 I/O points (CP1E-
@
14D
@
-
@
): 360g max.
CPU Unit with 20 I/O points (CP1E-
@
20D
@
-
@
): 370g max.
CPU Unit with 30 I/O points (CP1E-
@
30D
@
-
@
): 600g max.
CPU Unit with 40 I/O points (CP1E-
@
40D
@
-
@
): 660g max.
CPU Unit with 60 I/O points (CP1E-N60D
@
-
@
): 850g max.
CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D
@
-
@
): 680g max.
Electrical
specifications
Supply voltage
100 to 240 VAC 50/60 Hz
24 VDC
Operating voltage
range
85 to 264 VAC
20.4 to 26.4 VDC
Power consumption
15 VA/100 VAC max.
25 VA/240 VAC max.
(CP1E-E10D
@
-A/
@
14D
@
-A/
@
20D
@
-A)
9 W max. (CP1E-E10D
@
-D)
13 W max. (CP1E-N14D
@
-D/N20D
@
-D)
50 VA/100 VAC max.
70 VA/240 VAC max.
(CP1E-NA20D
@
-A/
@
30D
@
-A/
@
40D
@
-A/N60D
@
-A)
20 W max.
(CP1E-NA20D
@
-D/N30D
@
-D/N40D
@
-D/N60D
@
-D)
*
4
Inrush current
120 VAC, 20 A for 8 ms max. for cold start at room
temperature
240 VAC, 40 A for 8 ms max. for cold start at room
temperature
24 VDC, 30 A for 20 ms max. for cold start at room
temperature
External power supply
*
3
Not provided.
(CP1E-E10D
@
-A/
@
14D
@
-A/
@
20D
@
-A)
24 VDC, 300 mA
(CP1E-NA20D
@
-A/
@
30D
@
-A/
@
40D
@
-A/N60D
@
-A)
Not provided
Insulation resistance
20 M
Ω
min. (at 500 VDC) between the external AC
terminals and GR terminals
Except between DC primary current and DC
secondary current
Dielectric strength
2,300 VAC 50/60Hz for 1 min between AC external
and GR terminals Leakage current: 5 mA max.
Except between DC primary current and DC
secondary current
Power OFF detection
time
10 ms min.
2 ms min.
Application
environment
Ambient operating
temperature
0 to 55 °C
Ambient humidity
10% to 90%
Atmosphere
No corrosive gas.
Ambient storage
temperature
-20 to 75 °C (excluding battery)
Altitude
2,000 m max.
Pollution degree
2 or less: Conforms to JIS B3502 and IEC 61131-2.
Noise resistance
2 kV on power supply line (Conforms to IEC61000-4-4.)
Overvoltage category
Category II: Conforms to JIS B3502 and IEC 61131-2.
EMC Immunity Level
Zone B
Vibration resistance
Conforms to JIS 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s
2
for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)
Shock resistance
Conforms to JIS 60068-2-27.
147 m/s
2
, 3 times in X, Y, and Z directions
Terminal block
Fixed (not removable)
Terminal screw size
M3
Applicable standards
Conforms to EC Directive
Grounding method
Ground to 100
Ω
or less.