CP1E-E
@@
D
@
-
@
CP1E-N
@@
D
@
-
@/
NA20D
@
-
@
32
Optional Serial Communications Board for N30/40/60 or NA20 CPU Units
CP1W-CIF01 RS-232C Option Board
●
RS-232C Connector
CP1W-CIF11/CIF12 RS-422A/485 Option Board
●
RS-422A/485 Terminal Block
CP1E N30/40/60
or NA20 CPU Units
CP1W-CIF11/12
RS-422A/485 Option
Board
CP1W-CIF01
RS-232C Option
Board
Built-in
RS-232C port
Model number
Port
Maximum
transmission
distance
Connection method
CP1W-CIF01
One RS-232C port
15 m
Connector
(D-sub, 9 pin female)
CP1W-CIF11
One RS-422A/485 port
(not isolated)
50 m
Terminal block
(using ferrules)
CP1W-CIF12
One RS-422A/485 port
(isolated)
500 m
Terminal block
(using ferrules)
COMM
Front
Back
Communications Status Indicator
RS-232 Connector
CPU Unit Connector
Note:
Do not use the 5-V power from pin 6 of the RS-232C port for anything but CJ1W-CIF11 RS-422A Conversion
Adapter, NT-AL001 RS-232C/RS-422A Conversion Adapter and NV3W-M
@
20L Programmable Terminal.
The external device or the CPU Unit may be damaged.
Pin
Abbr.
Signal name
Signal direction
1
FG
Frame ground
--
2
SD (TXD)
Send data
Output
3
RD (RXD)
Receive data
Input
4
RS (RTS)
Request to send
Output
5
CS (CTS)
Clear to send
Input
6
5 V
Power supply
--
7
DR (DSR)
Data set ready
Input
8
ER (DTR)
Data terminal ready
Output
9
SG (0 V)
Signal ground
--
Connector hood
FG
Frame Ground
--
5
6
1
9
COMM
Front
Back
Communications Status Indicator
DIP Switch for
Operation Settings
RS-422A/485 Connector
RDA- RDB+ SDA- SDB+ FG
CPU Unit
Connector
RDB+
RDA-
SDA-
SDB+
FG
Tighten the terminal block screws
to a torque of 0.28 N·m.
Содержание SYSMAC CP1E-E10DR-A