237
Communications Frames
Section 6-8
Host Link FINS Protocol Conversion and Use of Network
Routing tables are required to enable the serial communications path to be
treated as a network. This is because with Host Link FINS, the FINS remote
node address is used to specify the target (communications partner PLC that
is the Host Link slave). Therefore, the node to which the Board/Unit is
mounted cannot always be specified, depending on the FINS remote node
address. To specify the Unit at the target requires the FINS remote unit
address. Therefore, the serial port cannot always be specified depending on
the FINS unit address.
The network address for the serial communications path is used to specify
from the network the node to which the Board/Unit is mounted and the serial
port. Therefore, routing tables must be used to enable the serial communica-
tions path to be treated as a network.
Host Link FINS Protocol Conversion and Use of Serial Connection
Routing tables are not required to enable serial communications paths to be
treated as networks. The serial port in the node can be specified without rout-
ing tables by specifying the network address as the unit address of the serial
port.
6-8
Communications Frames
6-8-1
CompoWay/F
Command Frame
Note
CompoWay/F commands use ASCII as the transmission code. Therefore, be
sure to use ASCII for the CompoWay/F command after the FINS command
code 2803 hex (from node number to text) using CMND(490) or other instruc-
tion.
Example: If the CompoWay/F command MRC SRC is “01” “02” (where the
quotation marks (“ ”) indicate ASCII characters), 0, 1, 0, 2 must be treated as
ASCII characters. Therefore, set “01” as 3031 hex (not 01 hex), and “02” as
3032 hex (not 02 hex).
Frame before Conversion
FINS header
FINS command
CompoWay/F
(See note.)
MRC
SRC
00 hex
28
03
Node No.
(
×
101)
(
×
102)
(ASCII code
2 bytes)
Sub-
address
"00"
(ASCII code
3030 hex)
etc.
SID
"0"
(ASCII
code
30 hex)
Command
(MRC, SRC)
(ASCII code
4 bytes)
Text
(ASCII code)
CompoWay/F
STX
(02 hex)
Node No.
(
×
101)
(
×
102)
(ASCII code
2 bytes)
Sub-
address
"00"
(ASCII code
3030 hex)
etc.
BCC
ETX
(03 hex)
Text
(ASCII code)
Command
(MRC, SRC)
(ASCII code
4 bytes)
SID
"0"
(ASCII
code
30 hex)
Frame after Conversion
Etc.
Remote
network
address
(DNA)
Remote
node
address
(DA1)
Remote
unit
address
(DA2)
Serial port
allocated
address
or local
network
address
or local
network
node
address
Serial
port unit
address
Содержание SYSMAC CJ1W-SCU21-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 89: ...60 Basic Operating Procedure Section 1 9...
Страница 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Страница 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Страница 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Страница 277: ...248 Communications Frames Section 6 8...
Страница 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Страница 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Страница 391: ...362 Introduction Appendix A...
Страница 421: ...392 CompoWay F Master Protocol Appendix B...
Страница 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Страница 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Страница 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Страница 627: ...598 ES100 Digital Controller Protocol Appendix K...
Страница 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Страница 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Страница 717: ...688 Visual Inspection System Protocol Appendix O...
Страница 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Страница 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Страница 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Страница 781: ...752 Revision History...