3

Nomenclature

ERR Indicator: Indicates communications errors.

COMM Indicator: ON while the Module is in data communication.
Power Indicator

Communications DIP Switch

The DIP switch is on the left-
hand side under the cover on
the upper part of the Remote
I/O Terminal.

Address Setting Switch

Set the rotary switch to the node
address by referring to the
following table.

I/O Indicators

M4 Mounting Screw

Terminal Cover
The Module stops operating with the
cover opened.

I/O and I/O Device Power Supply Terminals 8 to 15
These terminals will be used as output terminals 0
through 7 if the connected device handles both input
and output signals.
I/O and I/O Device Power Supply Terminals 0 to 7
These terminals will be used as input terminals if the
connected device handles both input and output
signals.

I/O Power Supply Terminals
Connect 24 VDC I/O power supply

Fixture Track
Used for DIN track mounting.

CompoBus/S Internal Power Supply
Terminals (BS+ and BS--)

CompoBus/S Communications Cable
Terminals (BDH and BDL)

3

INDICATORS

Indicator

Display

Color

Meaning

PWR

Lit

Green

The communications power supply is ON.

Not lit

The communications power supply is OFF.

COMM

Lit

Yellow

Normal communications

Not lit

A communications error has occurred or the Module is in standby status.

ERR

Lit

Red

A communications error has occurred.

Not lit

Normal communications or the Module is in standby status.

0 to 15

Lit

Yellow

The corresponding I/O signal is ON.

Not lit

The corresponding I/O signal is OFF.

3

DIP SWITCH SETTINGS

Pins 1 and 2 are reserved. The
default setting is always OFF.

Baud Rate Setting

Mode

Pin 3

Setting

Long distance

ON

Sets the I/O block to communicate in a long distance (500 m at 93.75 kbps) CompoBus/S system.

High speed

OFF (default)

Sets the I/O block to communicate in a high speed (750 kbps at 100 m) CompoBus/S system.

Output HOLD/CLEAR Mode

Mode

Pin 4

Setting

HOLD

ON

Output status is maintained.

CLEAR

OFF (default)

Output status is cleared when a communications error occurs.

Содержание SRT2-PD16T

Страница 1: ...nformation I O points I O classification Internal I O circuit common Rated voltage I O rated voltage Part number 16 Input NPN common 24 VDC 24 VDC SRT2 ID16T PNP common SRT2 ID16T 1 8 each Inputs and outputs NPN common SRT2 MD16T PNP common SRT2 MD16T 1 16 Output NPN common SRT2 OD16T PNP common SRT2 OD16T 1 3 ACCESSORIES Item Specification Part number Communications cable Flat cable 100 m length ...

Страница 2: ...x common Current consumption See Note 50 mA max at 24 VDC Connection method Multi drop method and T branch method Secondary branches cannot be connected to T branch lines Dielectric strength 500 VAC for 1 min between insulated circuits Noise immunity 1 5 kV with a pulse width of 100 ns to 1 µs Vibration resistance 10 to 150 Hz 1 0 mm double amplitude or 70 m s2 Shock resistance 200 m s2 Mounting s...

Страница 3: ...k Used for DIN track mounting CompoBus S Internal Power Supply Terminals BS and BS CompoBus S Communications Cable Terminals BDH and BDL 3 INDICATORS Indicator Display Color Meaning PWR Lit Green The communications power supply is ON Not lit The communications power supply is OFF COMM Lit Yellow Normal communications Not lit A communications error has occurred or the Module is in standby status ER...

Страница 4: ...ing Hex 0 0 6 6 12 C 1 1 7 7 13 D 2 2 8 8 14 E 3 3 9 9 15 F 4 4 10 A 5 5 11 B Note For node number settings refer to the CompoBus S Operation Manual W266 Dimensions Unit mm inch SRT2 ID16T 1 SRT2 MD16T 1 SRT2 OD16T 1 Mounting Holes Two 4 2 dia or M4 180 7 09 170 50 1 97 40 3 15 57 5 2 26 170 0 2 6 69 0 008 40 0 2 1 57 0 008 ...

Страница 5: ...pler Photocoupler Inputs 0 to 7 Outputs 0 to 7 DC DC converter isolated type Photocoupler Photocoupler Outputs 0 to 7 Outputs 8 to 15 I O power supply I O power supply I O power supply Internal circuit Internal circuit Internal circuit Internal circuit Internal circuit Internal circuit Voltage drop Voltage drop Voltage drop Voltage drop Voltage drop Voltage drop 3 EXTERNAL CONNECTIONS Input NPN Mo...

Страница 6: ... RIO 1 04 00 Specifications subject to change without notice Printed in U S A OMRON ELECTRONICS INC One East Commerce Drive Schaumburg IL 60173 NOTE DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters to inches divide by 25 4 1 800 55 OMRON OMRON CANADA INC 885 Milner Avenue Scarborough Ontario M1B 5V8 416 286 6465 9 ...

Отзывы: